INSP-Final Inspection | 12/16/2004 | 12/16/2004 | 12/16/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/16/2004 at 10:39:26 AM. Contact: ###-####. SE office area okay; aux drains will not be piped to exterior per Bill A.; awaiting west side of building to be completed for heads under stairs 12/16/2004 1:09:11 PM
|
INSP-Final Inspection | 12/16/2004 | 12/16/2004 | 12/16/2004 | P | PASS |
Rick Jackson
|
|
|
The permit is okay for final; the west side of building is under a different permit for shell and core 12/16/2004 1:16:32 PM
|
DOC - Permit Finaled | 12/16/2004 | 12/16/2004 | 12/16/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/16/2004 1:16:38 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/15/2004 | 12/15/2004 | 12/15/2004 | P | FAIL |
Rick Jackson
|
|
|
Adam; Phone #: ###-#### Internet Inspection Request from: Jan Rice Heads too close in SE office with broken hanger 12/15/2004 4:54:07 PM
|
Permit Ready to Issue | | | 11/17/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/17/2004 | | 11/17/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/17/2004 | | DONE |
|
|
|
Spoke with Julie and told her that this permit is ready & fees///11/17/04 9:40am BAS
|
Issue permit | | | 11/17/2004 | | |
|
|
|
|
Plan assigned to (Bill) | 10/20/2004 | | 11/16/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/26/2004 | | 11/16/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/16/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/26/2004 | | DONE |
|
|
|
|
Application received | | | 10/20/2004 | | |
|
|
|
|
Sprinkler Plan Check | 10/20/2004 | | 10/20/2004 | | FAIL |
Bill Alexander
|
|
|
1. Plans are incomplete. Provide clarification of correct fire sprinkler protection in Breakroom #111 (addresses on these plans as a "Kitchen"), Reception #100 (not identified in these plans). These rooms appear to have combustible soffits. Also they may have combustible cavities within the soffits? (NFPA 13:4.1.3, IFC 105.4, 901.2)
2. Plans are incomplete. Identify on these plans, Conference Room #115. (NFPA 13:4.1.3, IFC 105.4, 901.2)
3. Plans are incomplete. Identify on these plans, Conference Room #201. (NFPA 13:4.1.3, IFC 105.4, 901.2)
4. Plans are incomplete. Identify on these plans, Office #116. (NFPA 13:4.1.3, IFC 105.4, 901.2)
5. Provide a correct scale on the revised plans. (NFPA 13:4.1.3, IFC 105.4, 901.2)
|
Miscellaneous action | | | 10/20/2004 | | DONE |
|
|
|
Returned failed plans to permit desk for returning and required corrections.
|
Telephone call | | | 10/20/2004 | | |
|
|
|
Spoke with Gerald and told him that plans failed and need picked up///10/20/04 3:00pm BAS
|