Permit Information
Permit NumberFIR04-00664
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 7221 W POPLAR ST
Project NameSPR IDAHO YOUTH RANCH
Customer Number 
ePlanReview 
Description
IDAHO YOUTH RANCH, HAYS HOUSE II * To install a complete NFPA 13 fire sprinkler system within a new 7,450-ft/2, one story, wood framed, 20 resident group home and staff plus a 615-ft/2 wood framed garage. This permit also includes the underground fire service supply which will connect to an existing 6" C-900 PVC service tap at the property on the south side of W. Polar St. with a supervised Post Indicator Control Valve. Then it will run approximately 190+ feet S.W. into a mechanical room located on the S.E corner of the structure, under the footing and up through a finished floor, approximately 6" with 6" Ductile Iron and flange adapter fitting. All construction per the plans and attached review comment list. The fire sprinkler system (w/Q.R. heads throughout) is for a construction alternate allowing the corridors to be nonfire-resistive rated. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-03049.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/21/20059/22/20059/22/2005APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/16/20059/21/20059/21/2005PFAIL
DetailsTroy Cobbley
Provide signage on riser room door.
INSP-Final Inspection9/16/20059/16/20059/16/2005PFAIL
DetailsTroy Cobbley
Need signage on riser door, need test papers, signs on aux drains, certify backflow preventor, forward flush backflow preventor, provide head wrench.
INSP-Sprinkler Rough-in/Hydro8/10/20058/10/20058/10/2005PPART
DetailsTroy Cobbley
Hydro test for the wet system and anti-freeze loop passed. Contractor needs to provide test papers.
INSP-Sprinkler Rough-in/Hydro8/8/20058/9/20058/9/2005PFAIL
DetailsTroy Cobbley
Contact: Chris Lamb - Hydro Test Wet And Anti Freeze system; Phone #: ###-####
Hydro test of the anti-freeze loop failed and the overhead wet system would have passed if the piping from the check valve to the FDC had been included. Need to retest system
INSP-Supply line flush5/11/20055/11/20055/11/2005PPASS
DetailsTroy Cobbley
Inspection was for an underground hydro which passed
INSP-Supply line flush5/5/20055/10/20055/10/2005APASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in3/28/20053/29/20053/29/2005APART
DetailsTroy Cobbley
Ok to cover dificient areas as noted on approved plans 3/29/2005 12:29:55 PM
INSP-Sprinkler Rough-in3/24/20053/25/20053/25/2005APART
DetailsTroy Cobbley
See city approved plans for rooms that piping can be covered and for locations of deficiencies at these same rooms 3/25/2005 10:45:07 AM
INSP-Sprinkler Rough-in1/20/20051/21/20051/21/2005PPART
DetailsTroy Cobbley
Underground supply piping is ok to cover 1/21/2005 3:25:47 PM
Inspection Record Card- Fire12/1/2004 12/1/2004 DONE
Telephone call  12/1/2004 DONE
lft ms with recptionist ###-#### - permit is ready and no fee
Sprinkler Plan Check11/19/2004 11/30/2004 PASS
DetailsBill Alexander
Plan resubmittals received  11/19/2004 DONE
Plan assigned to (Bill)10/20/2004 11/3/2004 DONE
Sprinkler Plan Check10/20/2004 11/3/2004 PART
DetailsBill Alexander
1.Provide corrected plans for Area #3, Plan FP-2, of which the line pipe sizes are impossible to read.

2. Area #2, 3 and 4 are obstructed (in the most demanding/remote areas). All obstructed areas shall be identified on the plans. Provide a minimum 8.5 x 11's with the areas identified addressing the type of obstructed construction relating to each (if different).
PLANS/APPL TAKEN TO FRONT DESK  11/3/2004 DONE
Inspection Record Card- Fire11/3/2004 11/3/2004 DONE
Permit Ready to Issue  11/3/2004 DONE
Telephone call  11/3/2004 DONE
lft vm regarding fee and permit is ready to be picked up
Issue and Print Permit  11/3/2004 DONE
Application received  10/20/2004