INSP-Final Inspection | 2/9/2005 | 2/11/2005 | 2/11/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by Mary 2/11/2005 2:55:15 PM
|
DOC - Permit Finaled | 2/11/2005 | 2/11/2005 | 2/11/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 2/11/2005 2:55:21 PM
|
Telephone call | | | 1/11/2005 | | DONE |
|
|
|
Spoke with Jason and told him that permit is ready & fees///1/11/05 8:20am BAS
|
Issue permit | | | 1/11/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 11/15/2004 | | 1/10/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2005 | | DONE |
|
|
|
Called Jason Minnick (AEI) regarding the battery size for the NAC panel. He stated 7 a-h, the calculations (done for 60 hours) require a minimum of 9 a-h. He will fax over a revised calculation for 24 hours.
|
Plan resubmittals received | | | 1/10/2005 | | DONE |
|
|
|
Received revised battery calculation.
|
Alarm Plan Check | | | 1/10/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/10/2005 | | 1/10/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/7/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/17/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jason Minnick; AEI.
|
Application received | | | 11/15/2004 | | |
|
|
|
|