Permit Information
Permit NumberFIR04-00712
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 412 E PARKCENTER BLVD
Project Namealm - RIVER QUARRY BLDG C
Customer Number3RD FLOOR
ePlanReview 
Description
To relocate a manual pull station and provide total coverage notification (by adding new and relocating existing horn/strobes) to an existing fire alarm system. The required manual fire alarm system includes sprinkler monitoring, elevator recall/shutdown, door release, HVAC shutdown and notification throughout.

The associated building permit (BLD 04-02051) is to establish a new Certificate of Occupancy for AMRESCO and a Letter of Compliance for 'Vanilla Finish Space' (no tenant/no occupancy). Building is sprinklered for substitution of 1-hour construction. To perform selective demolition per plans; to construct new interior walls to create a non-rated corridor between the two existing stair enclosures and to create two tenant spaces from one. AMESCO will continue to occupy a smaller area of 12,000 sq. ft. and a new "Vanilla Finish" space of 4,816 sq. ft. will be created for future tenant. There will be approximately 2,575 sq. ft. new common area for use by both tenant spaces. PC04-577/drs ( AMRESCO & NEW 'VANILLA FINISH' TENANT SPACES)(RIVER QUARRY BLDG 'C' -3RD FLR)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20052/11/20052/11/2005PPASS
DetailsTroy Cobbley
Finaled by Mary 2/11/2005 2:55:15 PM
DOC - Permit Finaled2/11/20052/11/20052/11/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 2/11/2005 2:55:21 PM
Telephone call  1/11/2005 DONE
Spoke with Jason and told him that permit is ready & fees///1/11/05 8:20am BAS
Issue permit  1/11/2005 DONE
Plan assigned to (Mary)11/15/2004 1/10/2005 DONE
Telephone call  1/10/2005 DONE
Called Jason Minnick (AEI) regarding the battery size for the NAC panel. He stated 7 a-h, the calculations (done for 60 hours) require a minimum of 9 a-h. He will fax over a revised calculation for 24 hours.
Plan resubmittals received  1/10/2005 DONE
Received revised battery calculation.
Alarm Plan Check  1/10/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/10/2005 DONE
Permit Ready to Issue  1/10/2005 DONE
Inspection Record Card- Fire1/10/2005 1/10/2005 DONE
Plan resubmittals received  1/7/2005 DONE
Alarm Plan Check  11/17/2004 FAIL
Resubmittal required. Faxed comments to Jason Minnick; AEI.
Application received  11/15/2004