INSP-Final Inspection | 12/29/2004 | 12/29/2004 | 12/29/2004 | P | PASS |
Rick Jackson
|
|
|
Spacing maintained at 196 sq ft 12/29/2004 2:32:29 PM
|
DOC - Permit Finaled | 12/29/2004 | 12/29/2004 | 12/29/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/29/2004 2:32:33 PM
|
Inspection Record Card- Fire | 12/29/2004 | | 12/29/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/29/2004 | | DONE |
|
|
|
Spoke with Jeff and told him that permit is ready & fees///12/29/04 BAS
|
Miscellaneous action | | | 12/28/2004 | | DONE |
|
|
|
Returned 2nd submittal (corrected) plans to the Permit Desk for calling and returning.
|
Plan resubmittals received | | | 12/20/2004 | | |
|
|
|
|
Permit Ready to Issue | | | 11/30/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 11/30/2004 | | 11/30/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/30/2004 | | DONE |
|
|
|
Spoke with Jeff and told him that permit is ready & fees///11/30/04 11:10am BAS
|
Issue and Print Permit | | | 11/30/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/15/2004 | | 11/29/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/15/2004 | | 11/29/2004 | | PART |
Bill Alexander
|
|
|
1. Plan FP-1 is incomplete. Relocation of fire sprinklers does not address where the relocation started and does not determine meeting existing sprinkler design spacing limits for each room or area involved. Reference some related issues under detail addressed in item #2 below. (IFC 105.4, BMC 7-01-50:901.2)
2. Plan FP-1 is incomplete. Fire sprinklers are being added and the designer does not address where the added heads are connected nor does it address issues of adding sprinklers on an existing tree system and meeting the original system design spacing, heads on the same size piping, etc. (IFC 105.4, BMC 7-01-50:901.2)
3. No existing information provided on the system and existing plan submitted does not address the many of these issues. Provide approximate date the system was installed, area/level of work construction (NFPA 13:A.3.7) type, system type contractor is working on, existing fire sprinkler makes and model types, original area per sprinkler design, if the system had previously applied the "room design method", original ceiling height, new ceiling height/s, the number of fire sprinklers on the same size pipe allowed per original design unless the requirements of a "Room Design Method" are addressed and incorporated on the plans, etc., etc. (IFC 105.4, BMC 7-01-50:901.2)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/29/2004 | | DONE |
|
|
|
|
Application received | | | 11/15/2004 | | |
|
|
|
|
Sprinkler Plan Check | 12/20/2004 | | | | |
Bill Alexander
|
|
|
|