INSP-Final Inspection | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm permit finaled
|
INSP-Final Inspection | 8/15/2005 | 8/16/2005 | 8/16/2005 | P | FAIL |
Troy Cobbley
|
|
|
Relocate the a/v's in the existing restrooms to where shown on the plans. Test duct smoke detectors in the new area. Test the fire door in kitchen. Provide knox key box. Provide map at the facp. Dry system tripped ok but became plugged with something
|
CHANGE STATUS TO (ISS) | | | 8/15/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/15/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/12/2005 | | 8/12/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/12/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/12/2005 | | DONE |
|
|
|
tlk to ronnie ###-#### that permit and fees are ready to be picked and fees
|
Alarm Plan Check | | | 8/12/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/12/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/10/2005 | | DONE |
|
|
|
|
Case Summary | | | 8/10/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/22/2005 | | FAIL |
|
|
|
Resubmittal of sheets 2 and 4 are required.
|
Telephone call | | | 7/21/2005 | | DONE |
|
|
|
Phoned Ronnie at Simplex...Sheet 2, (battery calculations) has been plotted with shading, I can not read the quantities in the voltage drop calculations. He'll look into it and try to get new sheet down to the city.
|
Plan resubmittals received | | | 7/21/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/15/2005 | | DONE |
|
|
|
|
INSP-Conference | 7/14/2005 | 7/14/2005 | 7/14/2005 | P | DONE |
Troy Cobbley
|
|
|
I met George with Romar to discuss the location of the a/v located in the middle of the ramp to the stage. The a/v in question is ok as installed 1" too low.
|
Plan assigned to (Mary) | 11/16/2004 | | 12/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/23/2004 | | DONE |
|
|
|
Spoke with Chris Willis (Simplex), the packages of cut sheets are not complete. He will bring 4 additional copies down today.
|
Alarm Plan Check | | | 12/23/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/23/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 12/23/2004 | | |
|
|
|
|
(F) Reprint permit | | | 12/23/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/23/2004 | | 12/23/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/15/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/26/2004 | | FAIL |
|
|
|
Resubmittal required. Comments faxed to Chris Willis (Simplex) and John Rimbey (Mulder).
|
Application received | | | 11/16/2004 | | |
|
|
|
|