Permit Information
Permit NumberFIR04-00718
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 925 CLOVERDALE RD
Project Namealm boise valley adventist sch
Customer Number 
ePlanReview 
Description
To replace an existing required manual fire alarm system in the existing school and portables and extend the system into the new gymnasium and class addition. The required manual fire alarm system includes HVAC shutdown, area coverage (portables only), firefly door release and notification throughout.

IFC 907.2.1 Group A. A manual fire alarm system shall be installed in accordance with NFPA 72 in Group A occupancies having an occupant load of 300 or more. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm as required for the Group E occupancy.

The associated building permit (BLD 04-00709) is to construct a new 17,175 sq. ft. single story, Type VB, fully fire sprinklered gymnasium & class addition. The addition is considered as a separate building with a 2 hour fire wall separating the existing Type V1hr building. Other work includes all site improvements, paving and landscaping. All work is per approved plans and attachments. Fire sprinklers are used for area in the addition and the existing building shall also be fire sprinklered to satisfy IFC fire flow requirements.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20058/18/20058/18/2005PPASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Final Inspection8/15/20058/16/20058/16/2005PFAIL
DetailsTroy Cobbley
Relocate the a/v's in the existing restrooms to where shown on the plans. Test duct smoke detectors in the new area. Test the fire door in kitchen. Provide knox key box. Provide map at the facp. Dry system tripped ok but became plugged with something
CHANGE STATUS TO (ISS)  8/15/2005 DONE
(F) Reprint permit  8/15/2005 DONE
Inspection Record Card- Fire8/12/2005 8/12/2005 DONE
Permit Ready to Issue  8/12/2005 DONE
Telephone call  8/12/2005 DONE
tlk to ronnie ###-#### that permit and fees are ready to be picked and fees
Alarm Plan Check  8/12/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/12/2005 DONE
Plan resubmittals received  8/10/2005 DONE
Case Summary  8/10/2005 DONE
Alarm Plan Check  7/22/2005 FAIL
Resubmittal of sheets 2 and 4 are required.
Telephone call  7/21/2005 DONE
Phoned Ronnie at Simplex...Sheet 2, (battery calculations) has been plotted with shading, I can not read the quantities in the voltage drop calculations. He'll look into it and try to get new sheet down to the city.
Plan resubmittals received  7/21/2005 DONE
Plan resubmittals received  7/15/2005 DONE
INSP-Conference7/14/20057/14/20057/14/2005PDONE
DetailsTroy Cobbley
I met George with Romar to discuss the location of the a/v located in the middle of the ramp to the stage. The a/v in question is ok as installed 1" too low.
Plan assigned to (Mary)11/16/2004 12/23/2004 DONE
Telephone call  12/23/2004 DONE
Spoke with Chris Willis (Simplex), the packages of cut sheets are not complete. He will bring 4 additional copies down today.
Alarm Plan Check  12/23/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/23/2004 DONE
CHANGE STATUS TO (ISS)  12/23/2004  
(F) Reprint permit  12/23/2004 DONE
Inspection Record Card- Fire12/23/2004 12/23/2004 DONE
Plan resubmittals received  12/15/2004 DONE
Alarm Plan Check  11/26/2004 FAIL
Resubmittal required. Comments faxed to Chris Willis (Simplex) and John Rimbey (Mulder).
Application received  11/16/2004  
Inspection Record Card- Fire8/12/2005