Permit Information
Permit NumberFIR04-00730
StatusFinaled
Name MOUNTAIN ALARM
Site Address 607 W GROVE ST
Project Namealm - BASQUE BOARDING HOUSE
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system in an existing building that includes releasing a double interlocked pre-action sprinkler system and HVAC shutdown.

3/25/2005 - The scope has been revised to accommodate five (5) storage areas on the second floor that contain pre-action sprinkler heads but no temperature control. Smoke detectors were originally shown for initiating devices and will be changed out to heat detectors. (Addresses D16, (plans and riser indicate a smoke, PDS Fire Inspector to field verify heat detector is installed) D36, D23, D26 and D28).

The associated building permit (BLD 04-00896) is to perform restoration work to an existing historic building. Work is to include plaster repair, paint, wallpaper, window repair, a new HVAC system, electrical upgrades, and plumbing changes all per the approved drawings and the plan review report on file. The 1994 Uniform Code for Building Conservation (UCBC) shall be used to regulate this building. This building will be used as a museum with office use. Tours by the public will be under the supervision of staff. The size of tour groups will be small. A fire alarm system and a fire sprinkler system will be installed. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (CYRUS JACOBS / UBERUAGA BOARDINGHOUSE) This building will be fire sprinklered in lieu of exterior opening protection, in lieu of a basement enclosure, in lieu of stair enclosures, in lieu of fire-resistance-rated corridors, in lieu of shafts, and for story increase.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20057/28/20057/28/2005PPASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection5/31/20056/1/20056/1/2005 PART
DetailsForrest France
Final pending map at panel, signage at door to FACP, signal verification, and removal of temp. covers on detection devices.
INSP-Final Inspection5/5/20055/6/20055/6/2005AFAIL
DetailsForrest France
Fail inspection, tamper switch on OS&Y in pit activated waterflow alarm. Two PIV tamper switches need adjustment. Control valve tamper switch is incorrectly addressed as attic waterflow. Need to test remaining sprinkler alarms. Heat and smoke detector
INSP-Final Inspection4/28/20054/29/20054/29/2005PCANC
DetailsTroy Cobbley
lynda; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Issue and Print Permit  4/28/2005 DONE
Alarm Plan Check  4/27/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/27/2005 DONE
Permit Ready to Issue  4/27/2005 DONE
Telephone call  4/27/2005 DONE
tlk to lynde jones ###-#### that permit and fees are ready to be picked up
Plan resubmittals received  4/21/2005 DONE
INSP-Final Inspection3/28/20053/29/20053/31/2005PFAIL
DetailsForrest France
linda; Phone #: ###-#### Resubmittals needed, addressing has changed.
Inspection Record Card- Fire3/28/2005 3/28/2005 DONE
Issue and Print Permit  3/28/2005 DONE
Alarm Plan Check  3/24/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/24/2005 DONE
Plan resubmittals received  3/21/2005 DONE
Plan assigned to (Mary)11/23/2004 2/2/2005 DONE
Alarm Plan Check  2/2/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/2/2005 DONE
Permit Ready to Issue  2/2/2005 DONE
Inspection Record Card- Fire2/2/2005 2/2/2005 DONE
Telephone call  2/2/2005 DONE
Spoke with lynde and told her that permit is ready & fees///2/2/05 10:30am BAS
Issue and Print Permit  2/2/2005 DONE
Plan resubmittals received  1/26/2005 DONE
Alarm Plan Check  12/17/2004 FAIL
Resubmittal required. Faxed comments to Lynde Jones.
Plan resubmittals received  12/14/2004  
Alarm Plan Check  12/1/2004 FAIL
NO comments written at this time. The FA system is to control a double interlock pre-action system. The submittal did not reflect the correct listed means of releasing for the FACP chosen.

A complete resubmittal is required.

Three sets of plans left at the front for Lynde Jones to pick up.
Application received  11/23/2004  
Case Summary  11/23/2004  
Inspection Record Card- Fire3/28/2005