INSP-Final Inspection | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
INSP-Final Inspection | 5/31/2005 | 6/1/2005 | 6/1/2005 | | PART |
Forrest France
|
|
|
Final pending map at panel, signage at door to FACP, signal verification, and removal of temp. covers on detection devices.
|
INSP-Final Inspection | 5/5/2005 | 5/6/2005 | 5/6/2005 | A | FAIL |
Forrest France
|
|
|
Fail inspection, tamper switch on OS&Y in pit activated waterflow alarm. Two PIV tamper switches need adjustment. Control valve tamper switch is incorrectly addressed as attic waterflow. Need to test remaining sprinkler alarms. Heat and smoke detector
|
INSP-Final Inspection | 4/28/2005 | 4/29/2005 | 4/29/2005 | P | CANC |
Troy Cobbley
|
|
|
lynda; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Issue and Print Permit | | | 4/28/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/27/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/27/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/27/2005 | | DONE |
|
|
|
|
Telephone call | | | 4/27/2005 | | DONE |
|
|
|
tlk to lynde jones ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 4/21/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 3/28/2005 | 3/29/2005 | 3/31/2005 | P | FAIL |
Forrest France
|
|
|
linda; Phone #: ###-#### Resubmittals needed, addressing has changed.
|
Inspection Record Card- Fire | 3/28/2005 | | 3/28/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/28/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/24/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/24/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/21/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 11/23/2004 | | 2/2/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/2/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/2/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/2/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/2/2005 | | 2/2/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/2/2005 | | DONE |
|
|
|
Spoke with lynde and told her that permit is ready & fees///2/2/05 10:30am BAS
|
Issue and Print Permit | | | 2/2/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/26/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/17/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Lynde Jones.
|
Plan resubmittals received | | | 12/14/2004 | | |
|
|
|
|
Alarm Plan Check | | | 12/1/2004 | | FAIL |
|
|
|
NO comments written at this time. The FA system is to control a double interlock pre-action system. The submittal did not reflect the correct listed means of releasing for the FACP chosen.
A complete resubmittal is required.
Three sets of plans left at the front for Lynde Jones to pick up.
|
Application received | | | 11/23/2004 | | |
|
|
|
|
Case Summary | | | 11/23/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 3/28/2005 | | | | |
|
|
|
|