Description
To provide complete notification in the remodeled area (1st flr, MRI Remodel) and monitor a new FM 200 suppression panel for alarm, supervisory and trouble (installed by General Fire for the MRI computer room only). There is a Liebert (4650 cfm) that feeds the MRI computer room only, therefore no HVAC shutdown is required per the IMC 606.2, exception. The required manual fire alarm system includes HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 04-01865) is to (ST LUKES-CENTRAL-1ST FLR)(MRI REMODEL) Remodel existing 981 sq. ft. area to include MRI vault, replace existing MRI unit and remodel existing MRI computer room. Work includes selective demolition of raised flooring and infill of the sunklen area with concrete to be level with surounding floors; construction of new interior, non-bearing, non-combustible wall to create new work area from part of previous computer room; removal of exterior wall portion designed for removal & replacement for work / replacement of MRI unit in vault. PC04-522/drs-
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20051/21/20051/21/2005PCANC
DetailsRick Jackson
Rick, Jason at General Fire is replacing a defective FM-200 Panel. If he is successful this morning. I would like to final this project. There are just 2 smokes, 6 strobe NAC and the secondary monitoring of the FM-200 Panel. Thanks, Jim Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
INSP-Final Inspection1/21/20051/21/20051/21/2005PPASS
DetailsRick Jackson
DOC - Permit Finaled1/21/20051/21/20051/21/2005PPASS
DetailsRick Jackson
Finaled by inspector at 1/21/2005 2:32:51 PM
Permit Ready to Issue  12/15/2004 DONE
Inspection Record Card- Fire12/15/2004 12/15/2004 DONE
Telephone call  12/15/2004 DONE
lft vm jim shilton ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  12/15/2004 DONE
Plan assigned to (Mary)11/29/2004 12/14/2004 DONE
Alarm Plan Check  12/14/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  12/14/2004 DONE
Spoke with Roger from ECI regarding the Leibert (4650cfrm). He stated the unit feeds one space and IMC606.2 exception applies. I agree. NO HVAC shutdown required for the Leibert in the MRI computer room.
PLANS/APPL TAKEN TO FRONT DESK  12/14/2004 DONE
Telephone call  12/2/2004 DONE
Spoke with Jim Shilton, Honeywell, regarding the 4800cfm Liebert unit that is in the computer room. He is shown as monitoring the FM-200 panel only. What provisions are there for this cooling unit for shutdown? He will discuss with General Fire (FM-200 supplier/installer) and have them contact me.
Application received  11/29/2004  
Case Summary  11/29/2004 DONE