INSP-Final Inspection | 1/21/2005 | 1/21/2005 | 1/21/2005 | P | CANC |
Rick Jackson
|
|
|
Rick, Jason at General Fire is replacing a defective FM-200 Panel. If he is successful this morning. I would like to final this project. There are just 2 smokes, 6 strobe NAC and the secondary monitoring of the FM-200 Panel. Thanks, Jim Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
|
INSP-Final Inspection | 1/21/2005 | 1/21/2005 | 1/21/2005 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 1/21/2005 | 1/21/2005 | 1/21/2005 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/21/2005 2:32:51 PM
|
Permit Ready to Issue | | | 12/15/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/15/2004 | | 12/15/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/15/2004 | | DONE |
|
|
|
lft vm jim shilton ###-#### that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 12/15/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 11/29/2004 | | 12/14/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/14/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Telephone call | | | 12/14/2004 | | DONE |
|
|
|
Spoke with Roger from ECI regarding the Leibert (4650cfrm). He stated the unit feeds one space and IMC606.2 exception applies. I agree. NO HVAC shutdown required for the Leibert in the MRI computer room.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/14/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/2/2004 | | DONE |
|
|
|
Spoke with Jim Shilton, Honeywell, regarding the 4800cfm Liebert unit that is in the computer room. He is shown as monitoring the FM-200 panel only. What provisions are there for this cooling unit for shutdown? He will discuss with General Fire (FM-200 supplier/installer) and have them contact me.
|
Application received | | | 11/29/2004 | | |
|
|
|
|
Case Summary | | | 11/29/2004 | | DONE |
|
|
|
|