Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00744
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR SLRMC MRI REMODEL
Customer Number 
ePlanReview 
Description
(ST LUKES-CENTRAL-1ST FLR)(MRI REMODEL) To modify fire sprinkler protection for the remodel of an existing 981-ft/2 area for a MRI vault and remodel existing MRI computer room. Fire sprinkler work is related to construction of new interior, non-bearing, non-combustible wall for the creation of a new work area from part of previous computer room. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00744.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro2/10/20052/11/20052/11/2005APASS
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 2/10/2005 at 3:33:45 PM. Contact: ###-####.
DOC - Permit Finaled2/11/20052/11/20052/11/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 2/11/2005 12:24:59 PM
INSP-Sprinkler Rough-in/Hydro2/10/20052/10/20052/10/2005PFAIL
DetailsTroy Cobbley
Looked at tie in but could not inspect the rest of the work due to GE calibrating the MRI machine. 2/10/2005 1:33:50 PM
Issue and Print Permit  1/14/2005 DONE
Permit Ready to Issue  1/11/2005 DONE
Inspection Record Card- Fire1/11/2005 1/11/2005 DONE
Telephone call  1/11/2005 DONE
Spoke with Jeff and told him that permit is ready & fees///1/11/05 10:30am BAS
Sprinkler Plan Check1/4/2005 1/10/2005 PASS
DetailsBill Alexander
Plan assigned to (Bill)1/4/2005 1/10/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/10/2005 DONE
Plan resubmittals received  1/4/2005 DONE
INSP-Sprinkler Rough-in12/23/200412/27/200412/27/2004APART
DetailsRick Jackson
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Okay to cover MRI vault only; will verify required room separation at next phase 12/27/2004 11:17:29 AM
Permit Ready to Issue  12/21/2004 DONE
Inspection Record Card- Fire12/21/2004 12/21/2004 DONE
Telephone call  12/21/2004 DONE
Spoke with Greg and told him that permit is ready & fees///12/21/04 8:40am BAS
Issue and Print Permit  12/21/2004 DONE
Plan assigned to (Bill)12/2/2004 12/20/2004 DONE
DetailsBill Alexander
Sprinkler Plan Check12/15/2004 12/20/2004 PASS
DetailsBill Alexander
Construction must be verified.
PLANS/APPL TAKEN TO FRONT DESK  12/20/2004 DONE
Plan resubmittals received  12/15/2004 DONE
Telephone call  12/13/2004 DONE
called jeff t anderson ###-#### that his plan failed and needs to be returned to sender
Sprinkler Plan Check12/2/2004 12/10/2004 FAIL
DetailsBill Alexander
8:45AM. Problem with calcs/separation connected fitting, etc. Called Jeff Anderson, (gone). Jeff Packham is responding.

1. Plans are incomplete. Provide a facility location map addressing the area of work this scope of work is being performed.

2. The designer is not incorporating 11.2.3.2 and does not address the design implementing in this system addition/area. Reference each allowed addressed in NFPA 13:11.2.3.2, 11.2.3.3 and 11.2.3.4. Whichever the designer is implementing, it must be identifiable, clear, addressed correctly and fully. All related and pertinent information must be included substantiating acceptance of that design in the submittal package. Depending on the design implementing, construction information may be required (and addressed on the plan). If the area verifying is not the most demanding then provide verification of a most demanding and pipe accordingly, etc., etc.

3. Provide correct information regarding the "new" tap off an existing supply. Data submittal may be included to clarify what the designer's intent is.

4. Provide:
a. Type of (copper) pipe and fittings.
b. Whether soldering or brazing.
c. Type of solder or braze and braze flux using, (since each is addressed in the code specifically).

5. Identify the hanger connection to the structure (which requires to be listed).

6. Hangers on copper piping have different spacing requirements than carbon steel. Address this change on the plans.
Miscellaneous action  12/10/2004 DONE
Returned plans (less 1) to call desk for returning.
Application received  12/2/2004