INSP-Final Inspection | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/8/2005 | 11/9/2005 | 11/9/2005 | A | FAIL |
Troy Cobbley
|
|
|
provide spare heads for canopy for the head box, expansion tank model number does not match plans verify use, run 2" forward flush/drain to exterior.
|
CHANGE STATUS TO (ISS) | | | 11/8/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/8/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 10/5/2005 | | 11/8/2005 | | DONE |
Bill Alexander
|
|
|
|
Permit Ready to Issue | | | 11/1/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/1/2005 | | 11/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/1/2005 | | DONE |
|
|
|
Spoke with Diane and told her that permit is ready & fees///11/01/05 9:20am BAS
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/31/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/5/2005 | | 10/31/2005 | | PASS |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/10/2005 | 10/10/2005 | P | PASS |
Troy Cobbley
|
|
|
Hydro test for the outside canopy passed.
|
Plan resubmittals received | | | 10/5/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2005 | 7/8/2005 | 7/8/2005 | P | PART |
Troy Cobbley
|
|
|
Piping hydro tested from the point of connection to the backflow preventor and passed. Still need earthquake bracing installed on 3" supply main.
|
FIR-Aging Inspection | 5/5/2005 | 5/5/2005 | 5/6/2005 | | NR |
Troy Cobbley
|
|
|
work in progress
|
Issue permit | | | 2/3/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/3/2004 | | 1/26/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/21/2005 | | 1/26/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/26/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/26/2005 | | 1/26/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/26/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/26/2005 | | DONE |
|
|
|
tlk to secretary ###-#### that brad's permit and fees are ready to be picked up
|
Plan resubmittals received | | | 1/21/2005 | | |
|
|
|
|
Telephone call | | | 12/13/2004 | | DONE |
|
|
|
lft vm brad bettencourt - that permit needs to be returned to scope require a bld permit to attach with
|
Sprinkler Plan Check | 12/10/2004 | | 12/10/2004 | | FAIL |
Bill Alexander
|
|
|
1. We are returning your plans until you can provide a valid and approved building review/permit meeting IBC and IFC requirements.
The following is required in order to meet BMC 7-01-09 Paragraph 105.1.1.1 and International Fire Code 105.4 submittal requirements.
2. When resubmitting, provide a copy of the companies contract relating to the final accepted bids/prices settlement (include all change-orders, extras, etc., cost for verification of BCO ยง4-02-28(2-B) which reads: "When the installation of sprinkler heads is not involved or insignificant due to the type of work being permitted, a plan review fee equivalent to 1.05% of the total bid price shall be assessed, up to a maximum of $3,150 (whichever is larger), and paid to the building official."
3. Include data submittals on the expansion chamber identifying the size incorporating, etc.
4. Address the backflow "burp cup" drain and where it will be exhausted.
5. Clarify the hanger detail addressing the "HangerMate ZE710" and its UL and/or FM listing limits.
6. Provide canopy roof construction which includes type of truss, joist, and related, etc.
|
Telephone call | | | 12/10/2004 | | DONE |
|
|
|
Faxed letter back to Brad Bettencourt.
|
Application received | | | 12/3/2004 | | |
|
|
|
|