Permit NumberFIR04-00773
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12551 W EXECUTIVE DR
Project NameSPR OH VAN AUKER SHELL W.H.
Customer Number 
ePlanReview 
Description
RONALD VAN AUKER WAREHOUSE & OFFICE (SHELL ONLY) - To install a complete fire sprinkler system for High Hazard protection in a new 16,000-ft/2, enclosed one story, concrete tilt-up and steel shell warehouse and office building. This permit is for the construction of the shell building only. (Excluded 1,000-ft/2 roof covered storage area at the west side of the building was not included). There is no occupancy allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction per the approved plans and attached comment list. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-02121.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/19/20055/19/20055/19/2005PPASS
DetailsTroy Cobbley
fire sprinkler finaled
FIR-Aging Inspection5/10/20055/10/20055/10/2005 NR
DetailsTroy Cobbley
Work is in progress. Finals should be called in by end of month
Plan resubmittals received  3/24/2005 DONE
Backflow change
Sprinkler Plan Check3/24/2005 3/24/2005 DONE
Changed backflow from an Ames Colt to a Wikins 350 (6').
Miscellaneous action  3/24/2005 DONE
Emailed PDF file of stamped approval to Don Weland 3:10pm. Copied Troy Cobbley.
Issue and Print Permit  2/7/2005 DONE
Inspection Record Card- Fire2/4/2005 2/4/2005 DONE
Permit Ready to Issue  2/4/2005 DONE
Telephone call  2/4/2005 DONE
tlk to don weland ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check2/2/2005 2/3/2005 PASS
DetailsBill Alexander
Started review when designer/contractor called and requested to stop review and requests return plans, for changes to be submitted 2/3/2005. 2/2/2005, 3:25pm
Plan resubmittals received  2/3/2005 DONE
Plan assigned to (Bill)2/2/2005 2/3/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  2/3/2005 DONE
Plan resubmittals received  2/2/2005  
Started review when designer/contractor called and requested to stop review and requests return plans, for changes to be submitted 2/3/2005. 2/2/2005, 3:25pm
Telephone call  2/2/2005 DONE
Contractor (Stan Beus) called and requested not to review latest resubmittal (2/2/2005). He is making changes and will come down and pick them up.
Issue and Print Permit  1/10/2005 DONE
Permit Ready to Issue  1/7/2005 DONE
Inspection Record Card- Fire1/7/2005 1/7/2005 DONE
Telephone call  1/7/2005 DONE
Spoke with Don and told him that permit is ready & fees///1/7/05 9:45am BAS
Sprinkler Plan Check1/3/2005 1/6/2005 PART
DetailsBill Alexander
1. Plans are denied. Fire sprinkler listed use is outside the design allowed since storage is less than 36" of the fire sprinkler deflector. If dropping the storage to within 36" and 48", minimum required pressure (for these heads) will be 22-psi! Please reference the head listing data. Resubmit an approved design meeting minimum requirements.
January 6, 2005 - Designer is maintaining the listed use incorporating the Tyco Series "EC-25", SSP, 25.2 K-factor, (1"), TY9128 sprinklers. Hence, this system is not designed for a MAXIMUM allowable storage height, since scaling the drawings (no elevation dimensions provided on the building section view), appears to be 24' +- to the bottom of the roof support trusses? If the designer (with support of the building owner) requests to continue to incorporate this system design limitations, then approval will be restricted and the implementation of a PERMANENT marking system shall be employed throughout of this facility. Since no rule or wording has been officially adopted for marking systems, it shall be approved prior to installation, by the Fire Chief. (IFC 102.7)

2. Designer shall correlate all different designs to match the actual design providing and to be approved on all related plans and documents for consistency and future reference. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
January 6, 2005 - Addressed as corrected, with exception found on plan FP1 of 2 "Fire Sprinkler System Design Criteria," which does not correlate with calculations provided? Correct and resubmit.

3. Backflow prevention is not provided with required forward flow components/provisions. Provide forward flow test piping and appurtenance in accordance with NFPA 13:8.16.4.6.1*. Provide the size outlet matching the required pipe size verifying in the forward flow calculations. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
January 6, 2005 - Central Maintenance Kit (Figure 590F) is unacceptable since backflow test would then require putting the entire system out of service with a physical shutdown and draining. This test is not a service or repair process, but a test procedure. Revise and resubmit a design which will incorporate a forward flow test which will not remove this system from service.

January 6, 2005 - Added Review Comments/Requirements Relating To This Resubmittal:
4. All original submittals had been returned (excluding two) and those have been used for UG approval only, for City and ISRB records. Resubmit individual materials data sheets incorporating in this facility. These include, but may not be limited to:
a. Water supply certificate,
b. Manufacturer's fire sprinkler data information of all fire sprinkler heads incorporating in this structure, with each one specifically identified (if more than one choice is addressed),
c. Riser manifold and associated devices,
d. Seismic bracing calculations,
e. Backflow prevention device and appurtenance,
f. Wall P.I.,
g. FDC,
h. Outside alarm device,
i. Additional system control valves, etc.
(BMC 7-01-50:901.2, BMC 7-01-53:903.1.3, IFC 105.4.2)
Plan assigned to (Bill)1/3/2005 1/6/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/6/2005 DONE
Plan resubmittals received  1/3/2005 DONE
Issue and Print Permit  12/28/2004 DONE
Plan assigned to (Bill)12/15/2004 12/27/2004 DONE
Sprinkler Plan Check12/15/2004 12/27/2004 PART
DetailsBill Alexander
Allowed Underground Fire Service Supply Only
Overhead Probles:
1. Plans are denied. Fire sprinkler listed use is outside the design allowed since storage is less than 36" of the fire sprinkler deflector. If dropping the storage to within 36" and 48", minimum required pressure (for these heads) will be 22-psi! Please reference the head listing data. Resubmit an approved design meeting minimum requirements.

2. Designer shall correlate all different designs to match the actual design providing and to be approved on all related plans and documents for consistency and future reference. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)

3. Backflow prevention is not provided with required forward flow components/provisions. Provide forward flow test piping and appurtenance in accordance with NFPA 13:8.16.4.6.1*. Provide the size outlet matching the required pipe size verifying in the forward flow calculations. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)

4. Modified backflow system control valve must be on the supply side of the backflow assembly itself, unless approved by the water purveyor. Provide approval or resubmit with modified plans to reflect installation requirements. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)

5. Provide or show how a reliable heat and lighting source will be provided for the fire sprinkler riser room. Heat shall be provided to maintain a minimum 40ºF temperature. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2, NFPA 13:7.2.5.2.1)

6. Sammy© and similar fastening systems (which are not specifically addressed in NFPA 13), shall be installed under their listing limits. They are not listed for all system component applications. Provide installation listing requirements on the plans, addressing the application use in this permit. Note the installation diagram below, which does not address metal pan connections as shown. Reference the manufacturer's minimum thickness requirements also (not shown). (IFC 105.4, 901.2)

7. Information on supporting the fire sprinkler mains attached to parallel to structural members (trusses) is lacking. Mains solely supported by single trusses and/or beams shall be verified structurally and approved by the Architect prior to attachment loading. Provide some reference of approval acceptable to allow the mains to be supported as provided. If incorporating trapeze hangers, they shall be engineered and addressed on the plans. (IBC 102.4, 102.7, 102.8, 104.7.2, 105.4.2, 1604.3, 1604.4, NFPA 13:9.1.1.2)
PLANS/APPL TAKEN TO FRONT DESK  12/27/2004 DONE
Permit Ready to Issue  12/27/2004 DONE
Inspection Record Card- Fire12/27/2004 12/27/2004 DONE
Telephone call  12/27/2004 DONE
Spoke with Don and told him that permit is ready & fees///11:00am 12/27/04 BAS
Application received  12/15/2004