INSP-Final Inspection | 5/19/2005 | 5/19/2005 | 5/19/2005 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler finaled
|
FIR-Aging Inspection | 5/10/2005 | 5/10/2005 | 5/10/2005 | | NR |
Troy Cobbley
|
|
|
Work is in progress. Finals should be called in by end of month
|
Plan resubmittals received | | | 3/24/2005 | | DONE |
|
|
|
Backflow change
|
Sprinkler Plan Check | 3/24/2005 | | 3/24/2005 | | DONE |
|
|
|
Changed backflow from an Ames Colt to a Wikins 350 (6').
|
Miscellaneous action | | | 3/24/2005 | | DONE |
|
|
|
Emailed PDF file of stamped approval to Don Weland 3:10pm. Copied Troy Cobbley.
|
Issue and Print Permit | | | 2/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/4/2005 | | 2/4/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/4/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/4/2005 | | DONE |
|
|
|
tlk to don weland ###-#### that permit and fees are ready to be picked up
|
Sprinkler Plan Check | 2/2/2005 | | 2/3/2005 | | PASS |
Bill Alexander
|
|
|
Started review when designer/contractor called and requested to stop review and requests return plans, for changes to be submitted 2/3/2005. 2/2/2005, 3:25pm
|
Plan resubmittals received | | | 2/3/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/2/2005 | | 2/3/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/3/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/2/2005 | | |
|
|
|
Started review when designer/contractor called and requested to stop review and requests return plans, for changes to be submitted 2/3/2005. 2/2/2005, 3:25pm
|
Telephone call | | | 2/2/2005 | | DONE |
|
|
|
Contractor (Stan Beus) called and requested not to review latest resubmittal (2/2/2005). He is making changes and will come down and pick them up.
|
Issue and Print Permit | | | 1/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/7/2005 | | 1/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/7/2005 | | DONE |
|
|
|
Spoke with Don and told him that permit is ready & fees///1/7/05 9:45am BAS
|
Sprinkler Plan Check | 1/3/2005 | | 1/6/2005 | | PART |
Bill Alexander
|
|
|
1. Plans are denied. Fire sprinkler listed use is outside the design allowed since storage is less than 36" of the fire sprinkler deflector. If dropping the storage to within 36" and 48", minimum required pressure (for these heads) will be 22-psi! Please reference the head listing data. Resubmit an approved design meeting minimum requirements.
January 6, 2005 - Designer is maintaining the listed use incorporating the Tyco Series "EC-25", SSP, 25.2 K-factor, (1"), TY9128 sprinklers. Hence, this system is not designed for a MAXIMUM allowable storage height, since scaling the drawings (no elevation dimensions provided on the building section view), appears to be 24' +- to the bottom of the roof support trusses? If the designer (with support of the building owner) requests to continue to incorporate this system design limitations, then approval will be restricted and the implementation of a PERMANENT marking system shall be employed throughout of this facility. Since no rule or wording has been officially adopted for marking systems, it shall be approved prior to installation, by the Fire Chief. (IFC 102.7)
2. Designer shall correlate all different designs to match the actual design providing and to be approved on all related plans and documents for consistency and future reference. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
January 6, 2005 - Addressed as corrected, with exception found on plan FP1 of 2 "Fire Sprinkler System Design Criteria," which does not correlate with calculations provided? Correct and resubmit.
3. Backflow prevention is not provided with required forward flow components/provisions. Provide forward flow test piping and appurtenance in accordance with NFPA 13:8.16.4.6.1*. Provide the size outlet matching the required pipe size verifying in the forward flow calculations. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
January 6, 2005 - Central Maintenance Kit (Figure 590F) is unacceptable since backflow test would then require putting the entire system out of service with a physical shutdown and draining. This test is not a service or repair process, but a test procedure. Revise and resubmit a design which will incorporate a forward flow test which will not remove this system from service.
January 6, 2005 - Added Review Comments/Requirements Relating To This Resubmittal:
4. All original submittals had been returned (excluding two) and those have been used for UG approval only, for City and ISRB records. Resubmit individual materials data sheets incorporating in this facility. These include, but may not be limited to:
a. Water supply certificate,
b. Manufacturer's fire sprinkler data information of all fire sprinkler heads incorporating in this structure, with each one specifically identified (if more than one choice is addressed),
c. Riser manifold and associated devices,
d. Seismic bracing calculations,
e. Backflow prevention device and appurtenance,
f. Wall P.I.,
g. FDC,
h. Outside alarm device,
i. Additional system control valves, etc.
(BMC 7-01-50:901.2, BMC 7-01-53:903.1.3, IFC 105.4.2)
|
Plan assigned to (Bill) | 1/3/2005 | | 1/6/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/6/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/3/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/28/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/15/2004 | | 12/27/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/15/2004 | | 12/27/2004 | | PART |
Bill Alexander
|
|
|
Allowed Underground Fire Service Supply Only
Overhead Probles:
1. Plans are denied. Fire sprinkler listed use is outside the design allowed since storage is less than 36" of the fire sprinkler deflector. If dropping the storage to within 36" and 48", minimum required pressure (for these heads) will be 22-psi! Please reference the head listing data. Resubmit an approved design meeting minimum requirements.
2. Designer shall correlate all different designs to match the actual design providing and to be approved on all related plans and documents for consistency and future reference. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
3. Backflow prevention is not provided with required forward flow components/provisions. Provide forward flow test piping and appurtenance in accordance with NFPA 13:8.16.4.6.1*. Provide the size outlet matching the required pipe size verifying in the forward flow calculations. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
4. Modified backflow system control valve must be on the supply side of the backflow assembly itself, unless approved by the water purveyor. Provide approval or resubmit with modified plans to reflect installation requirements. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2)
5. Provide or show how a reliable heat and lighting source will be provided for the fire sprinkler riser room. Heat shall be provided to maintain a minimum 40ºF temperature. (BMC 7-01-50 revised paragraph 901.2, BMC 7-01-53 new paragraph 903.1.3, IFC 105.4.2, NFPA 13:7.2.5.2.1)
6. Sammy© and similar fastening systems (which are not specifically addressed in NFPA 13), shall be installed under their listing limits. They are not listed for all system component applications. Provide installation listing requirements on the plans, addressing the application use in this permit. Note the installation diagram below, which does not address metal pan connections as shown. Reference the manufacturer's minimum thickness requirements also (not shown). (IFC 105.4, 901.2)
7. Information on supporting the fire sprinkler mains attached to parallel to structural members (trusses) is lacking. Mains solely supported by single trusses and/or beams shall be verified structurally and approved by the Architect prior to attachment loading. Provide some reference of approval acceptable to allow the mains to be supported as provided. If incorporating trapeze hangers, they shall be engineered and addressed on the plans. (IBC 102.4, 102.7, 102.8, 104.7.2, 105.4.2, 1604.3, 1604.4, NFPA 13:9.1.1.2)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/27/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/27/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/27/2004 | | 12/27/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/27/2004 | | DONE |
|
|
|
Spoke with Don and told him that permit is ready & fees///11:00am 12/27/04 BAS
|
Application received | | | 12/15/2004 | | |
|
|
|
|