INSP-Final Inspection | 4/28/2005 | 4/28/2005 | 4/28/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/16/2005 | 3/17/2005 | 3/17/2005 | A | PASS |
Troy Cobbley
|
|
|
Sprinkler piping in the admitting area is ok to cover. 3/17/2005 10:36:26 AM
|
Plan assigned to (Bill) | 2/25/2005 | | 2/28/2005 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/25/2005 | | 2/28/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/28/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/28/2005 | | 2/28/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/28/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/28/2005 | | DONE |
|
|
|
tlk to brodie ###-#### that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 2/28/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/25/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2005 | 1/11/2005 | 1/11/2005 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 1/11/2005 at 8:48:50 AM. Contact: ###-####. Okay to cover; still need verification for 3 heads off 1 inch 1/11/2005 4:50:14 PM
|
Plan assigned to (Bill) | 12/22/2004 | | 1/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/5/2005 | | 1/7/2005 | | PASS |
Bill Alexander
|
|
|
Fielf verify original system design conformance to design submitted.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/7/2005 | | 1/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/7/2005 | | DONE |
|
|
|
called brodie that his permit and fees are ready to be picked up
|
Issue and Print Permit | | | 1/7/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/5/2005 | | |
|
|
|
|
Sprinkler Plan Check | 12/22/2004 | | 12/30/2004 | | FAIL |
Bill Alexander
|
|
|
1. Plans are incomplete. Provide existing line locations with location of taps or relocating positions. (BMC 7-01-50:901.2, IFC 105.4.2)
2. Plans are incomplete. Provide ceiling elevations for all suspended ceilings. (BMC 7-01-50:901.2, IFC 105.4.2)
3. System layout/design does not meet minimum code. Fire sprinkler protection requires the wetting of all walls. Provide corrected plans meeting minimum fire protection requirements. (BMC 7-01-50:901.2, IFC 105.4.2, 104.3, 106, 107.2.2, 901.6, 903.3.3)
|
Telephone call | | | 12/30/2004 | | DONE |
|
|
|
Left message for Broadie that plans failed and need picked up///12/30/04 2:00pm BAS
|
Application received | | | 12/22/2004 | | |
|
|
|
|