Permit Information
Permit NumberFIR04-00793
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR ST LUKES-1S ADMITTING
Customer Number 
ePlanReview 
Description
(ST LUKES-1S ADMITTING) To add and modify fire sprinklers for the remodel of a 2,230-ft/2 area located in the 1st floor, south wing for the admitting and financial counseling offices. Fire sprinkler work is associated with the construction of new smoke partitions and suspended ceiling grid systems. This building is fully sprinklered for occupancy use requirements. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01142.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20054/28/20054/28/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Sprinkler Rough-in/Hydro3/16/20053/17/20053/17/2005APASS
DetailsTroy Cobbley
Sprinkler piping in the admitting area is ok to cover. 3/17/2005 10:36:26 AM
Plan assigned to (Bill)2/25/2005 2/28/2005 DONE
DetailsBill Alexander
Sprinkler Plan Check2/25/2005 2/28/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/28/2005 DONE
Inspection Record Card- Fire2/28/2005 2/28/2005 DONE
Permit Ready to Issue  2/28/2005 DONE
Telephone call  2/28/2005 DONE
tlk to brodie ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  2/28/2005 DONE
Plan resubmittals received  2/25/2005 DONE
INSP-Sprinkler Rough-in/Hydro1/11/20051/11/20051/11/2005PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/11/2005 at 8:48:50 AM. Contact: ###-####. Okay to cover; still need verification for 3 heads off 1 inch 1/11/2005 4:50:14 PM
Plan assigned to (Bill)12/22/2004 1/7/2005 DONE
Sprinkler Plan Check1/5/2005 1/7/2005 PASS
DetailsBill Alexander
Fielf verify original system design conformance to design submitted.
PLANS/APPL TAKEN TO FRONT DESK  1/7/2005 DONE
Inspection Record Card- Fire1/7/2005 1/7/2005 DONE
Permit Ready to Issue  1/7/2005 DONE
Telephone call  1/7/2005 DONE
called brodie that his permit and fees are ready to be picked up
Issue and Print Permit  1/7/2005 DONE
Plan resubmittals received  1/5/2005  
Sprinkler Plan Check12/22/2004 12/30/2004 FAIL
DetailsBill Alexander
1. Plans are incomplete. Provide existing line locations with location of taps or relocating positions. (BMC 7-01-50:901.2, IFC 105.4.2)

2. Plans are incomplete. Provide ceiling elevations for all suspended ceilings. (BMC 7-01-50:901.2, IFC 105.4.2)

3. System layout/design does not meet minimum code. Fire sprinkler protection requires the wetting of all walls. Provide corrected plans meeting minimum fire protection requirements. (BMC 7-01-50:901.2, IFC 105.4.2, 104.3, 106, 107.2.2, 901.6, 903.3.3)
Telephone call  12/30/2004 DONE
Left message for Broadie that plans failed and need picked up///12/30/04 2:00pm BAS
Application received  12/22/2004