INSP-Final Inspection | 12/15/2005 | 12/15/2005 | 12/15/2005 | P | PASS |
Forrest France
|
|
|
Underground fire supply line finaled.
|
INSP-Sprinkler Rough-in/Hydro | 12/9/2005 | 12/12/2005 | 12/12/2005 | A | DEFR |
Forrest France
|
|
|
mike Note: 24 hr air test; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles NOTE: Wrong permit number called in, this was meant for FIR05-00385 for the overhead, not under FIR04-00812 for the associated UG supply.
|
INSP-Sprinkler Rough-in | 11/3/2005 | 11/4/2005 | 11/4/2005 | P | PART |
Forrest France
|
|
|
2nd floor corridor hard lid and 1st floor restrooms hard lid are okay to cover for overhead rough-in.
|
INSP-Supply line flush | 8/9/2005 | 8/9/2005 | 8/9/2005 | A | PART |
Forrest France
|
|
|
Two hour hydrostatic test and supply line flush both passed inspection.
|
INSP-Supply line flush | 7/27/2005 | 7/27/2005 | 7/27/2005 | A | FAIL |
Forrest France
|
|
|
Underground fire supply work appears to be installed in a satisfactory manner, however the resubmitted plans and notes with scope of work does not address phase 2 (connection to city supply) work. This work must be submitted and approved prior to field inspection and sign off.
|
Plan resubmittals received | | | 7/26/2005 | | DONE |
|
|
|
|
INSP-Supply line flush | 1/18/2005 | 1/19/2005 | 1/19/2005 | A | PART |
Rick Jackson
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice UG stub out only - okay; used one piece riser 1/19/2005 10:10:01 AM
|
Issue permit | | | 1/10/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/30/2004 | | 1/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/7/2005 | | 1/7/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/7/2005 | | 1/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/7/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/6/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/5/2005 | | DONE |
|
|
|
Spoke with Jeff and told him that plans failed and need picked up////1/5/04 8:00am BAS
|
Sprinkler Plan Check | 12/30/2004 | | 1/4/2005 | | FAIL |
Bill Alexander
|
|
|
1. Underground tap is unacceptable with Boise City Fire Department and agreements with United Water, (unless verification from United Water is provided that the hydrant tapped main will be extended through the parking lot to another supply connection or extend and loop back to the street main). Provide a separate tap off the street main and extend it into the building for the fire sprinkler supply. (BMC 7-01-46:IFC 508.6)
|
Application received | | | 12/30/2004 | | |
|
|
|
|