INSP-Final Inspection | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/1/2005 4:04:34 PM
|
INSP-Final Inspection | 1/24/2005 | 1/25/2005 | 1/25/2005 | P | FAIL |
Troy Cobbley
|
|
|
Provide immediate shutdown for the hvac units. Provide the correct remote annunciator for the duct smoke detectors. Provide verification that the duct system over the lobby area has duct detector or that it is not required. 1/25/2005 3:35:44 PM
|
Issue permit | | | 1/11/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 12/30/2004 | | 1/7/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/7/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/7/2005 | | 1/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/7/2005 | | DONE |
|
|
|
tlk to charlie bayne ###-#### that his permit and fees are ready to be picked up
|
Application received | | | 12/30/2004 | | |
|
|
|
|