INSP-Final Inspection | 3/9/2005 | 3/10/2005 | 3/10/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 3/10/2005 1:44:30 PM
|
DOC - Permit Finaled | 3/10/2005 | 3/10/2005 | 3/10/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/10/2005 1:44:34 PM
|
Plan resubmittals received | | | 3/9/2005 | | PASS |
Bill Alexander
|
|
|
Field modifications verification. Changes attached to original approved documents.
|
Miscellaneous action | | | 3/9/2005 | | DONE |
|
|
|
Emailed copy of documents and approval 3:20pm.
|
INSP-Final Inspection | 3/7/2005 | 3/8/2005 | 3/8/2005 | A | FAIL |
Troy Cobbley
|
|
|
Approved fire sprinkler plans do not match installation. Pendants have been deleted in the door pockets, upright heads added under ductwork and in void spaces. 90's have been added in the 3" supply. I could not get access to verify tie in to the existing 3" feed. Auxillary drain has been added above the ceiling at the end of the new 3" main. Resubmit plans or verify if as builts will be acceptable for the changes. 3/8/2005 4:40:06 PM
|
INSP-Sprinkler Rough-in | 1/31/2005 | 1/31/2005 | 1/31/2005 | P | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore hydro okay 1/31/2005 4:02:49 PM
|
Telephone call | | | 1/11/2005 | | DONE |
|
|
|
Spoke with Greg and told him that permit is ready & fees///1/11/05 8:15am BAS
|
Issue and Print Permit | | | 1/11/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/5/2005 | | 1/10/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/5/2005 | | 1/10/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/10/2005 | | 1/10/2005 | | DONE |
|
|
|
|
Application received | | | 1/5/2005 | | |
|
|
|
|