Permit Information
Permit NumberFIR05-00029
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 5208 W IRVING ST
Project NameSPR WAREHOUSE BLD@5208 IRVING
Customer Number 
ePlanReview 
Description
WAREHOUSE BUILDING @ 5208 IRVING * To install a complete fire sprinkler system which includes the underground fire service supply and overhead piping in an existing warehouse building. This building has the height to accommodate high piled combustible storage of which fire protection meeting requirements of Boise Municipal Code 7-01-56-903.1.6. The proposed fire sprinkler design is solely for the intended tenancy of Boise City Police Department with a protection design for Ordinary Group 2 Occupancy Hazard use with warehouse limitation. Request for the reduced alternative protection is addressed in an attached letter on file from Doug Bagley, Property Manager. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not associated to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/26/20071/29/20071/29/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/9/20071/10/20071/10/2007AFAIL
DetailsTroy Cobbley
See city approved plans for items still needing completed.
INSP-Final Inspection1/2/20071/3/20071/3/2007AFAIL
DetailsTroy Cobbley
There were not approved and updated plans on site for the inspection.
Issue and Print Permit  8/22/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/21/2006 DONE
Permit Ready to Issue  8/21/2006 DONE
Inspection Record Card- Fire8/21/2006 8/21/2006 DONE
Telephone call  8/21/2006 DONE
spoke to john@###-####/told permit was ready, permit#, project name & address, and fee
Sprinkler Plan Check  8/16/2006 PASS
As-builts reviewed/approved by B. Johnson
Plan resubmittals received  7/26/2006 DONE
Plan mod to reflect field installation changes.
INSP-Final Inspection2/13/20062/14/20062/14/2006AFAIL
DetailsTroy Cobbley
See city approved plans for deficiencies which include resubmitting plans for piping changes in the second floor storage room remote area. The riser is missing items for the final such as stickers and the backflow preventor is incorrect.
Permit Ready to Issue  2/13/2006 DONE
Telephone call  2/13/2006 DONE
tlk to john warnick - ###-#### that permit and fees are ready to be picked up
(F) Reprint permit  2/13/2006 DONE
CHANGE STATUS TO (ISS)  2/13/2006 DONE
already issued previously
Sprinkler Plan Check1/24/2006 2/10/2006 PASS
Plans re submittals reviewed and accepted pending satisfactory field verification by PDS fire inspector. See attached comments.
PLANS/APPL TAKEN TO FRONT DESK  2/10/2006 DONE
Plan resubmittals received  1/24/2006 DONE
INSP-Supply line flush1/10/20061/10/20061/10/2006PPASS
DetailsTroy Cobbley
Underground supply line flush passed.
INSP-Sprinkler Rough-in/Hydro1/4/20061/5/20061/5/2006APASS
DetailsTroy Cobbley
overhead / underground hydro passed
CHANGE STATUS TO (ISS)  1/4/2006 DONE
already pd previously
Sprinkler Plan Check12/28/2005 12/30/2005 PART
DetailsBill Alexander
Plan corrections have not been made. This submittal is for one head added only.
Plan assigned to (Bill)12/28/2005 12/30/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/30/2005 DONE
Permit Ready to Issue  12/30/2005 DONE
Telephone call  12/30/2005 DONE
left mess that permit is ready
Plan resubmittals received  12/28/2005 DONE
INSP-Sprinkler Rough-in10/17/200510/17/200510/17/2005PPASS
DetailsTroy Cobbley
Underground supply line is ok to cover
INSP-Sprinkler Rough-in10/3/200510/4/200510/4/2005APART
DetailsTroy Cobbley
Office area only is ok to cover. Two upright sprinkler heads are blocked by duct work as marked on the approved plans. This will need to be fixed prior to final.
Inspection Record Card- Fire8/25/2005 8/25/2005 DONE
Permit Ready to Issue  8/25/2005 DONE
Telephone call  8/25/2005 DONE
tlk to john ###-#### that permit and fees are ready to be picked up
Issue permit  8/25/2005  
Plan assigned to (Bill)8/9/2005 8/24/2005 DONE
Sprinkler Plan Check8/15/2005 8/24/2005 PART
DetailsBill Alexander
Reference Review Comments
PLANS/APPL TAKEN TO FRONT DESK  8/24/2005 DONE
Plan resubmittals received  8/15/2005 DONE
Telephone call  8/11/2005 DONE
customer took failed plans
Sprinkler Plan Check7/28/2005 8/10/2005 FAIL
DetailsBill Alexander
Telephone call  8/10/2005 DONE
tlk to john warnick that permit failed and ready to be picked up
Plan resubmittals received  7/28/2005  
Permit EXPIRED  5/2/2005 DONE
Telephone call  3/17/2005 DONE
Per Sam plans failed/ contractor came in & picked them up///JRR
Sprinkler Plan Check3/4/2005 3/10/2005 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  3/10/2005 DONE
Returned documents to fron permit desk for calling and returning.
Telephone call  3/10/2005 DONE
tlk to john warnick that fire permit needs plan resubmitted required cmc
Meeting  3/7/2005 DONE
Office meeting with Sam Rogers reviewing request and decided it should be the Fire Marshals decision per BMC 7-01-56 AMENDMENT ADDING SECTION 903.1.6, HIGH PILED COMBUSTIBLE STORAGE WAREHOUSE, Add a Section 903.1.6, which reads: "It shall be the responsibility of the code official to evaluate all requests for a system layout meeting the requirements for a less hazardous storage configuration."
Telephone call  3/7/2005 DONE
Left message (cell) Jerry Prinzing, for call back regarding "Spec Warehouse" review approval 2:45pm.
Plan resubmittals received  3/4/2005 DONE
Letter from Doug Bagley, (Bagley-Bushgel Buildings), through John Warnick (Commercial Fire Protection), requesting approval as stated.
Miscellaneous action  3/4/2005 DONE
Sent letter with (City copy) plan for verification/approval to Sam Rogers.
Sprinkler Plan Check2/1/2005 2/8/2005 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Case Summary  2/8/2005 DONE
Inspection Record Card- Fire2/8/2005 2/8/2005 DONE
Telephone call  2/8/2005 DONE
left mess that permit has failed and needs to be picked up
Plan resubmittals received  2/1/2005 DONE
Sprinkler Plan Check1/13/2005 1/19/2005 FAIL
DetailsBill Alexander
Requires a meeting to go over materials submitted.

1/25/2005, 10:30AM. Met with Ray Lopez and went over submitted drawing problems in meeting minimum submittal, design, installation, code and review requirements. Returned all drawing except 1 set.
Telephone call  1/19/2005 DONE
to tlk secretary for john ###-#### that his permit has failed and needs to be picked up
Application received  1/13/2005  
Case Summary  1/13/2005 DONE