Case Summary | | | 7/30/2008 | | |
|
|
|
|
Case Summary | | | 3/3/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/3/2008 | | DONE |
|
|
|
|
INSP-Final Inspection | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled. Remainder of required building upgrade work to be completed via separate tenant permits.
|
Miscellaneous action | | | 12/7/2007 | | DONE |
|
|
|
Attached this permit to Building Permit BLD03-02412 Project # PRJ05-06247 per Sam Rogers
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | PART |
Forrest France
|
|
|
Testing completed for notification devices at the basement, first and third floors, also completed initiating device testing including all smoke detectors, ansul kitchen system, waterflow, pull station. Final pending the installation of notification devices at floors, rooms and areas currently occupied but indicated on the plans as "unoccupied" and therefore are missing required coverage. See clouded red lines on approved set for locations at the basement, 1st, 2nd and 4th floors.
|
INSP-Conference | 11/26/2007 | 11/26/2007 | 11/26/2007 | P | DONE |
Forrest France
|
|
|
Job scheduling.
|
INSP-Final Inspection | 11/19/2007 | 11/21/2007 | 11/21/2007 | A | PART |
Forrest France
|
|
|
Tested notification devices for the 1st thru 4th floors, no access provided for some areas on the 3rd and 1st floors-will need to retest, need to remove one existing SD at the 4th floor, noted on plans devices tested today including SD's and one pull station, fire doors at some locations are not adjusted correctly for full closure, need to test remainder of initiation devices and a/v's at next inspection.
|
Alarm Plan Check | | | 10/11/2007 | | PASS |
|
|
|
Fire Alarm Review 5th 2007 NFPA 72 Solid Joist Construction changes used.
|
Plan assigned to (Mike) | 10/8/2007 | | 10/11/2007 | | PASS |
|
|
|
10/11/2007 09:45:10 MWT - activity updated through activity FIRA22 from case FIR05-00033.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/11/2007 | | |
|
|
|
Ready for Re-Issue
|
Inspection Record Card- Fire | 10/11/2007 | | 10/11/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/11/2007 | | DONE |
|
|
|
left vm for charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/11/2007 | | DONE |
|
|
|
|
(F) Reprint permit | | | 10/11/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/11/2007 | | |
|
|
|
|
Plan resubmittals received | | | 10/8/2007 | | |
|
|
|
received 1 application, 3 material lists 1 copy of sheet 1,2,3,4,5,6, of 11 and 2 copys of sheets 7,8,9,10,11 sent to fire
|
Telephone call | | | 1/24/2007 | | DONE |
|
|
|
telcon and email with Rich Lewis, Rolf Jensen Associates (###-####) regarding spacing requirements for smoke detectors in the corridor having open ceiling joists over 12" deep. I agreed to consider using the 2007 ed of NFPA 72 as an alternate design for this particular situation.
|
Telephone call | | | 1/19/2007 | | DONE |
|
|
|
Telcon from Rich Lewis, Rolf Jensen, Walnut Creek ###-####, to discuss smoke detector requirements for ceilings of open solid joists more than 12" deep. I referenced NFPA 72, 5.7.3.2.4 (B)(2). We agree that paragraph applied but he was looking for "a more reasonable approach". I indicated we must follow prescribed code or an approved alternate design stamped by a professional engineer adn that we are willing to consider such an engineered alternate design as prescribed by the IFC, using a second engineer of our choice to verify the proposed design, to be paid for by the owner. He indicated he would suggest that alternative to the general contractor who he was working for.
|
INSP-Final Inspection | 7/10/2006 | 7/10/2006 | 7/10/2006 | P | PART |
Forrest France
|
|
|
C/N items from the previous inspection have been verified for completion, tested main FACP batteries, AC loss, phone lines, smoke above panel, need to provide locks at breakers, tested tamper switches, flow switches, addresses at flows do not match map or actual location. SD, manual pulls and notification to be tested at next inspection request. Duct detector testing is complete.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 7/10/2006 | | |
|
|
|
|
INSP-Final Inspection | 6/26/2006 | 6/29/2006 | 6/29/2006 | A | FAIL |
Forrest France
|
|
|
Tested all duct detectors today, one detector(device 30) in the basement failed to function, one detector on the 2nd floor will need to be relocated as it is upstream of a return grill, need to change descriptor of one detector location at the cafe ole office area. Noted that the SD's located adjacent to the atrium in several locations will not function as installed due to open ceiling beam obstructions greater than 12" in depth.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 6/26/2006 | | |
|
|
|
|
Case Summary | | | 6/23/2006 | | |
|
|
|
|
FIR-Aging Inspection | 5/30/2006 | 5/30/2006 | 6/5/2006 | | DONE |
Forrest France
|
|
|
Work in progress.
|
Miscellaneous action | | | 6/1/2006 | | DONE |
|
|
|
Called Charlie to notify of the required 3 hour fire separation (no smoke requried) between the two buildings and inform him that the smoke detectors for the atruim coverage are mounted on open beam ceilings (6 areas) and believe the beams to be 12" or greater, which means improper smoke detector coverage.
|
Alarm Plan Check | | | 2/28/2006 | | PASS |
|
|
|
Plan Modification. See scope for modifications. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/28/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/28/2006 | | DONE |
|
|
|
lft vm with chris willis ###-#### that permit and fees are ready to be picked up
|
Inspection Record Card- Fire | 2/28/2006 | | 2/28/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/28/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/15/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 3/28/2005 | | |
|
|
|
|
Issue permit | | | 3/28/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 1/18/2005 | | 3/18/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/18/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/18/2005 | | 3/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/18/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/11/2005 | | |
|
|
|
|
Alarm Plan Check | | | 3/2/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Chris Willis (Simplex) and Jon Van Stone (E2).
|
Plan resubmittals received | | | 2/14/2005 | | DONE |
|
|
|
|
Case Summary | | | 2/14/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/7/2005 | | FAIL |
|
|
|
No comments written, met with Jeff (E2 Co) to define deficiencies and the unoccupied spaces. Resubmittal required.
|
Application received | | | 1/18/2005 | | |
|
|
|
|