Case Summary | | | 3/3/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/3/2008 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/10/2006 | 8/11/2006 | 8/11/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler inspection passed, permit finaled.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 8/2/2006 | | |
|
|
|
|
Miscellaneous action | | | 7/27/2006 | | |
|
|
|
plans picked up from 2nd review, permit already issued status
|
(F) Reprint permit | | | 7/27/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/18/2006 | | 7/26/2006 | | PASS |
Bill Alexander
|
|
|
As Built
|
Miscellaneous action | | | 7/26/2006 | | DONE |
|
|
|
Took Modified plans to permit desk for releasing. 2nd review, no fee.
|
Telephone call | | | 7/26/2006 | | DONE |
|
|
|
spoke to randy@###-####/told permit was ready, permit#, address & project name, and no fees
|
Plan resubmittals received | | | 7/18/2006 | | |
|
|
|
|
Case Summary | | | 4/13/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 2/23/2005 | 2/23/2005 | 2/23/2005 | P | PART |
Troy Cobbley
|
|
|
With Bill Alexander's permission the remodeled restroom fire sprinklers appear ok. Resubmittals will be required before final will be given. 2/24/2005 9:53:07 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2005 | 2/22/2005 | 2/22/2005 | P | CANC |
Troy Cobbley
|
|
|
Tile workers were installing the floor so there is no access at this time. 2/22/2005 4:03:24 PM
|
INSP-Sprinkler Rough-in | 2/11/2005 | 2/11/2005 | 2/11/2005 | P | FAIL |
Troy Cobbley
|
|
|
Floor plan does not match fire sprinkler plans. Piping sizing on plan does not match field. Quick responce and standard responce heads are mixed and different temperatures from listing on plans. Sidewall head too far from ceiling. One pendant not installed yet. Two uprights blocked by new soffits. Inspection stopped. Plans need to be resubmitted. 2/11/2005 4:17:02 PM
|
Issue and Print Permit | | | 1/26/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/19/2005 | | 1/25/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/19/2005 | | 1/25/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/25/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/25/2005 | | 1/25/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/25/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/25/2005 | | DONE |
|
|
|
lft mes with secretary ###-#### that permit and fees are ready to picked up
|
Application received | | | 1/19/2005 | | |
|
|
|
|
INSP-Final Inspection | 8/2/2006 | 8/3/2006 | | P | |
Forrest France
|
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|