INSP-Final Inspection | 4/18/2006 | 4/18/2006 | 4/18/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm passed final inspection, permit finaled.
|
INSP-Final Inspection | 2/28/2005 | 3/1/2005 | 3/1/2005 | A | PART |
Troy Cobbley
|
|
|
Temporary occupancy given. Fire alarm panel and NAC panels inspected. Duct detectors on the sixth floor inspected. Induct detectors at main supply and returns on first through sixth floor inspected. Pull stations on all floors inspected. Audio visuals on sixth floor and first floor lobby inspected. Individual a/v's on first through sixth and basement inspected. All sprinkler monitoring points inspected. All other items not inspected. Plans will need to be resubmitted with changes which include ceiling mounted a/v's, deletion of pull on sixth floor, additional heat in penthouse and relocated NAC panels. 3/1/2005 2:53:41 PM
|
INSP-Final Inspection | 2/28/2005 | 2/28/2005 | 2/28/2005 | P | FAIL |
Troy Cobbley
|
|
|
Items tested included annunciation, manual pull stations and induct smoke detectors for common supply/returns for 2nd - 6th floors. Also tested duct smoke detectors on hvac units on 6th floor only. Tested all tamper switches and flow switches for basement through penthouse. Items still needing testing for temporary occupancy are elevator recall for the new elevators, induct detectors on first floor and duct detectors in penthouse and NAC supervision 2/28/2005 4:06:07 PM
|
INSP-Final Inspection | 2/23/2005 | 2/25/2005 | 2/25/2005 | A | FAIL |
Troy Cobbley
|
|
|
terri ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is not ready for testing 2/25/2005 2:08:54 PM
|
INSP-Alarm Testing | 2/18/2005 | 2/24/2005 | 2/24/2005 | A | CANC |
Troy Cobbley
|
|
|
terri ###-####
|
INSP-Final Inspection | 2/23/2005 | 2/24/2005 | 2/24/2005 | A | CANC |
Troy Cobbley
|
|
|
terri ###-####
|
Plan assigned to (Mary) | 1/26/2005 | | 2/17/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/17/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/17/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/17/2005 | | 2/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2005 | | DONE |
|
|
|
Spoke with Rob and told him that permit is ready & fees////2/17/05 8:30am BAS
|
Issue and Print Permit | | | 2/17/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/10/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/1/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten 2/1
|
Plan assigned to (Mary) | 1/31/2005 | | 1/31/2005 | | DONE |
|
|
|
|
Application received | | | 1/26/2005 | | |
|
|
|
|