INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 6/24/2005 | 6/27/2005 | 6/27/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in is good for cover, need all escutcheons on before final.
|
INSP-Sprinkler Rough-in | 6/21/2005 | 6/21/2005 | 6/21/2005 | P | FAIL |
Forrest France
|
|
|
Provide hanger at 2nd floor arm over greater than 2' in length, add head 2nd floor as shown on plans beyond tenant demising wall.
|
Issue and Print Permit | | | 6/20/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 6/20/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/1/2005 | | 6/17/2005 | | PASS |
Bill Alexander
|
|
|
06/17/2005-Provided calrifications.
EMAIL to Matt Kahns-6/6/2005 (no response)
6/9/2005
1. Relating to the above project are the Tyco Series TY-FRB EC HSW submittals that is not addressed on the plan sprinkler head legends? Is this the added head installed under a stairs?
Is this the only head?
2. The "Skylight" protection appears to be inadequate. The skylights are over 32-ft/2 and shall have correct sprinkler protection. The position of the deflector shall meet requirements of 8.5 "Position, Location, Spacing, and Use of Sprinklers." Inspector will verify deflector position in each.
|
Plan assigned to (Bill) | 6/1/2005 | | 6/17/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/17/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 6/17/2005 | | 6/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/17/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Telephone call | | | 6/17/2005 | | DONE |
|
|
|
will pickup later
|
Miscellaneous action | | | 6/9/2005 | | DONE |
|
|
|
Returned failed modified plans to permit desk for returning
|
Telephone call | | | 6/9/2005 | | DONE |
|
|
|
lft vm for matthew kahns ###-#### that permit failed and needed to be picked up
|
Plan resubmittals received | | | 6/1/2005 | | DONE |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 5/4/2005 | | DONE |
|
|
|
Recieved documentation of changes in the field which require covering. Modifications will follow with resubmittal plan prior to permit final. Documents attached to permit.
|
Plan resubmittals received | | | 5/3/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 2/24/2005 | 2/24/2005 | 2/24/2005 | P | PART |
Troy Cobbley
|
|
|
See approved plans for locations of piping above hard lids ok to cover. 2/24/2005 3:37:24 PM
|
Issue permit | | | 2/22/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/16/2005 | | 2/16/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/16/2005 | | DONE |
|
|
|
lft message with receptionist that permit and fees are ready to be picked up for matt kahns
|
Sprinkler Plan Check | 2/14/2005 | | 2/15/2005 | | PASS |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 2/14/2005 | | 2/15/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/15/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/14/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/11/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/3/2005 | | 2/10/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/3/2005 | | 2/10/2005 | | PART |
Bill Alexander
|
|
|
Allowed work on the 2nd floor only (with corrections also).
1. The first floor (FP1 of 2) spacing of sprinklers exceeds 130-ft/2 as originally designed in many areas that would be designated OH Occupancy areas. Some of these areas found (but may not be limited to) are, Assembly #104, Demo #101, Demo #102, Finish Product Storage #103, and an area not identified but extends from the Assembly #104.
2. Address (detail) the hanger attachments (FP1 and FP2 of 2), which must be listed and/or specifically addressed in NFPA 13 Chapter 9.
3. Plan FP2 of 2. Provide information and corrections "open office" skylight and correct rerouting pipe sizes to match origignal design.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/10/2005 | | 2/10/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/10/2005 | | DONE |
|
|
|
Spoke with Alicia told her that permit is ready & fees///2/10/05 BAS
|
Application received | | | 2/3/2005 | | |
|
|
|
|