Permit Information
Permit NumberFIR05-00072
StatusFinaled
Name AEI
Site Address 4709 W STATE ST
Project Namealm COLLISTER COMMUNITY CHURCH
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown and notification throughout. (Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow.)

The associated building permit (BLD 04-02139) is to have an addition will be have 5, 640 sq. ft. one story, type VB fully fire sprinklered with new fire alarm. Existing building will have some minor interior remodeling at the vestibule, classrooms and office areas per approved plans. Other work includes all site improvements, landscaping and paving per approved plans and attachments, DRH04-00160, CUP04-00076. Fire sprinklers used for area and additional story in the existing building. COLLISTER COMMUNITY CHURCH ADDITION AND DEMO OF A RESIDENTIAL STRUCTURE AND STORAGE BLDG.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/26/20059/26/20059/26/2005PPASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Sprinkler Rough-in/Hydro9/23/20059/26/20059/26/2005PPASS
DetailsTroy Cobbley
This was for a fire alarm inspection not a sprinkler rough-in. Fire alarm permit finaled
INSP-Final Inspection9/22/20059/23/20059/23/2005PFAIL
DetailsTroy Cobbley
Monitoring station did not receive zone 9 duct smoke detector signals. Batteries must be atleast 8.5 AH to meet 24 hour requirements. Label the remote annunciators as discussed. Provide NFPA 72 forms.
Alarm Plan Check9/23/2005 9/23/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/23/2005 DONE
Permit Ready to Issue  9/23/2005 DONE
Inspection Record Card- Fire9/23/2005 9/23/2005 DONE
Telephone call  9/23/2005 DONE
Spoke with Michael and told him permit is ready & fees///9/23/05 8:40am BAS
Issue and Print Permit  9/23/2005 DONE
Plan resubmittals received  9/22/2005 DONE
INSP-Final Inspection9/15/20059/16/20059/16/2005AFAIL
DetailsTroy Cobbley
Zones and riser location does not match plans. Resubmit to city. Only items tested are the sprinkler devices which are ok
FIR-Aging Inspection7/5/20057/5/20057/7/2005 NR
DetailsTroy Cobbley
Per Jason work is in progress
Inspection Record Card- Fire4/5/2005 4/5/2005 DONE
Permit Ready to Issue  4/5/2005 DONE
Telephone call  4/5/2005 DONE
tlk to jason minnick that permit and fees are ready to be picked up
Issue permit  4/5/2005 DONE
Plan assigned to (Mary)2/8/2005 4/4/2005 DONE
Alarm Plan Check  4/4/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/4/2005 DONE
Plan resubmittals received  3/17/2005 DONE
Alarm Plan Check  2/17/2005 FAIL
Resubmittal required. Faxed comments to Wes Smith, Romar.
Application received  2/8/2005  
Case Summary  2/8/2005 DONE
Telephone call  2/8/2005 DONE
Phoned to discuss the application with Wes, he was out of the office, I explained to Sandy that the FA permit application was incomplete and I needed to fax it back, she stated to fax it and ATTN Sandy.
Miscellaneous action  2/8/2005 DONE
Faxed the incomplete application to Sandy.