INSP-Final Inspection | 9/26/2005 | 9/26/2005 | 9/26/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 9/23/2005 | 9/26/2005 | 9/26/2005 | P | PASS |
Troy Cobbley
|
|
|
This was for a fire alarm inspection not a sprinkler rough-in. Fire alarm permit finaled
|
INSP-Final Inspection | 9/22/2005 | 9/23/2005 | 9/23/2005 | P | FAIL |
Troy Cobbley
|
|
|
Monitoring station did not receive zone 9 duct smoke detector signals. Batteries must be atleast 8.5 AH to meet 24 hour requirements. Label the remote annunciators as discussed. Provide NFPA 72 forms.
|
Alarm Plan Check | 9/23/2005 | | 9/23/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2005 | | 9/23/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2005 | | DONE |
|
|
|
Spoke with Michael and told him permit is ready & fees///9/23/05 8:40am BAS
|
Issue and Print Permit | | | 9/23/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/22/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | FAIL |
Troy Cobbley
|
|
|
Zones and riser location does not match plans. Resubmit to city. Only items tested are the sprinkler devices which are ok
|
FIR-Aging Inspection | 7/5/2005 | 7/5/2005 | 7/7/2005 | | NR |
Troy Cobbley
|
|
|
Per Jason work is in progress
|
Inspection Record Card- Fire | 4/5/2005 | | 4/5/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/5/2005 | | DONE |
|
|
|
|
Telephone call | | | 4/5/2005 | | DONE |
|
|
|
tlk to jason minnick that permit and fees are ready to be picked up
|
Issue permit | | | 4/5/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 2/8/2005 | | 4/4/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/4/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/4/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/17/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/17/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Wes Smith, Romar.
|
Application received | | | 2/8/2005 | | |
|
|
|
|
Case Summary | | | 2/8/2005 | | DONE |
|
|
|
|
Telephone call | | | 2/8/2005 | | DONE |
|
|
|
Phoned to discuss the application with Wes, he was out of the office, I explained to Sandy that the FA permit application was incomplete and I needed to fax it back, she stated to fax it and ATTN Sandy.
|
Miscellaneous action | | | 2/8/2005 | | DONE |
|
|
|
Faxed the incomplete application to Sandy.
|