Permit Information
Permit NumberFIR05-00076
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 301 S CAPITOL BLVD
Project NameBODO BUILDING 7 ALARM
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system (building is slated for A1, A2, B and M occupancies). The required manual fire alarm system includes sprinkler monitoring, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 04-01324) is to construct a new 135,950 square foot, three story, noncombustible, fully fire sprinklered shell building for future multi-plex theater, offices, retail and restaurant tenants. The new building is being constructed with non separated uses with the A-1 Occupancy being the most restrictive. The fire sprinkler system is being used for area increase. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permit are required to finish this building for occupancy. All construction per the approved plans and attached comment list. #04-386/JCM BoDo - Building #7 (Shell) -
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/10/20063/13/20063/13/2006APASS
DetailsForrest France
Required items on the correction notice have been completed, shell and core fire alarm permit finaled.
INSP-Final Inspection2/27/20062/28/20062/28/2006PFAIL
DetailsForrest France
Need to post building map showing roof plan including clock tower, update plans and 1st floor map to show changed EOL location from device 8:8.
INSP-Alarm Testing11/22/200511/23/200511/23/2005PPART
DetailsForrest France
The north elevator alarm devices tested okay.
INSP-Alarm Testing11/22/200511/22/200511/22/2005PCANC
DetailsForrest France
CHANGE STATUS TO (ISS)  11/22/2005 DONE
already pd previously
Permit Ready to Issue  11/21/2005 DONE
Inspection Record Card- Fire11/21/2005 11/21/2005 DONE
Telephone call  11/21/2005  
Called & told Kurt permit was ready to pick up on 11-21-05 @ 2:57 CW
Plan resubmittals received  11/18/2005 DONE
Nick with Synergy brought revised sheets to place in the submittals.
Alarm Plan Check  11/18/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/18/2005 DONE
Alarm Plan Check  11/17/2005 FAIL
Resubmittal required. No comments written, spoke to Nick at Synergy.

The FSD as shown in elevator #3 does not exist. It is still included on the plans.

A single tamper switch is shown for the fire pump items, etc. Nick will up date these at the same time and bring in new sheets to insert into the existing submittal.
INSP-Final Inspection11/10/200511/10/200511/10/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanniman's permission until resubmittals and elevator are finished and finaled. Elevator is not to be used until inspected.
INSP-Alarm Testing11/9/200511/9/200511/9/2005PPART
DetailsForrest France
The north elevator remains to be completed and tested, final pending verification of resubmittals for field changes.
Plan resubmittals received  11/3/2005  
INSP-Sprinkler Rough-in10/27/200510/28/200510/28/2005APART
DetailsForrest France
North elevator is still non-functional, provide resubmittals for all required changes.
INSP-Alarm Testing10/24/200510/25/200510/25/2005PFAIL
DetailsForrest France
North elevator is not functional at this time, need an additional SD above the FACP due to a beam pocket obstruction, clock tower AV is not functional, provide signage at FACP room door, outside bell to be relocated at face of brick, elevator roof damper is not required due to barometric shaft, resubmitt for changed EOL, added devices, deleted damper and revised matrix for pump, provide audibility for the FACP room.
INSP-Alarm Testing10/24/200510/24/200510/24/2005APART
DetailsForrest France
Partial shell alarm inspection only.
INSP-Alarm Testing10/21/200510/21/200510/21/2005PFAIL
DetailsForrest France
Lower pull station to 48" AFF, provide additional smoke at the panel due to beam blockage, verify audibility in the FACP room, fire pump run shows as an alarm and the matrix indicates a supervisory, change label at roof tamper and stair flow 108, outside bell shall silence upon waterflow ceasation, all sprinkler alarms tested today, no other items tested at this time.
Alarm Plan Check  10/14/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/14/2005 DONE
Inspection Record Card- Fire10/14/2005 10/14/2005 DONE
Permit Ready to Issue  10/14/2005 DONE
Telephone call  10/14/2005 DONE
left mess that permit is ready
Issue permit  10/14/2005 DONE
Plan resubmittals received  10/6/2005 DONE
Nick Schafer (Synergy) red-lined riser for changes.
Plan resubmittals received  9/29/2005  
Alarm Plan Check  9/26/2005 FAIL
NO comments written. Elevator requires two firemans hat and a revised matrix is required.
Plan resubmittals received  9/16/2005 DONE
Alarm Plan Check  9/12/2005 FAIL
Resubmittal required. Nick Schafer (Synergy) stated he needed to add input for a fire pump. I explained to him that he also needed to change his design to horn/strobe notification in all areas except the theatre. (Apparently the theatre is "isolated" from the rest of the building.)
Plan assigned to (Mary)9/12/2005 9/12/2005 DONE
Plan resubmittals received  8/26/2005 DONE
Miscellaneous action  8/12/2005 DONE
NOTE to PDS Fire Inspector. The elevators in BODO 7 are missing the required smoke detector at the top of the shaft (per Idaho Elevator Inspector), I am working with the engineer to get thei issue resolved. I don't believe it will pass the elevator inspection, but if it does, please do NOT final this permit until we have this issue resolved. THANKS
Plan assigned to (Mary)2/9/2005 4/12/2005 DONE
Inspection Record Card- Fire4/12/2005 4/12/2005 DONE
Permit Ready to Issue  4/12/2005 DONE
Telephone call  4/12/2005 DONE
tlk to kurt lechtenberg ###-#### that permit and no fee
CHANGE STATUS TO (ISS)  4/12/2005 DONE
Issue and Print Permit  4/12/2005 DONE
Alarm Plan Check  4/12/2005 PASS
Approved pending field inspection of fire alarm permit comments.
Plan resubmittals received  4/4/2005 DONE
Miscellaneous action  3/14/2005 DONE
PLANS ON HOLD pending additional information. ELevator has been defined as a traction elevator with the equipment in the pit and cables to the top. The FA plans are incorrect as there is no machine room. Nick at Synergy is working on getting additional information from the sprinkler contractor.
Plan resubmittals received  3/7/2005 DONE
Alarm Plan Check  2/23/2005 FAIL
Resubmittal required. Faxed comments to Kurt Lechtenberg 2/23.
Application received  2/9/2005  
Case Summary  2/9/2005 DONE
Inspection Record Card- Fire11/21/2005