INSP-Final Inspection | 11/10/2005 | 11/10/2005 | 11/14/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm permit finaled
|
INSP-Final Inspection | 11/10/2005 | 11/14/2005 | 11/14/2005 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
INSP-Alarm Testing | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
Plan resubmittals received | | | 11/2/2005 | | DONE |
|
|
|
REceived the correct information for the in-duct detector via fax from Bryan.
|
Alarm Plan Check | | | 11/2/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/2/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/2/2005 | | 11/2/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/2/2005 | | DONE |
|
|
|
E-mailed Paul that permit is ready & fees///11/2/05 9:15am BAS
|
(F) Reprint permit | | | 11/2/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/2/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/2/2005 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/1/2005 | | DONE |
|
|
|
Received an incorrect cut sheet for the in-duct detector. (Edwards panel, cut sheet was for the Pyrotronics).
|
Plan resubmittals received | | | 10/19/2005 | | DONE |
|
|
|
Received 1 transmittal letter, & 3 copys of Fire alarm calcs 3 copys of sheets FAO,FA2.1.1,FA2.1.2, FA5.1,FA5.2 Taken to Mary F.
|
Alarm Plan Check | | | 10/10/2005 | | FAIL |
|
|
|
Talked to John James on the phone.
Items to be addressed in the resubmittal:
1) All addressing is correct.
2) Revise matrix as required.
3) Submit cut sheets
4) Duct detector shown for FSD. either have the FSD shut down with the RF, or provide an in-duct detector.
|
Plan assigned to (Mary) | 10/10/2005 | | 10/10/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/6/2005 | | DONE |
|
|
|
Left a message for John W. James to call me (designer MTI).
|
Plan resubmittals received | | | 9/26/2005 | | |
|
|
|
|
INSP-Alarm Testing | 9/12/2005 | 9/13/2005 | 9/13/2005 | A | FAIL |
Forrest France
|
|
|
Resubmitt plans reflecting correct device addressing, duct detector #46 failed to shut down upon smoke detection.
|
INSP-Alarm Testing | 9/7/2005 | 9/8/2005 | 9/12/2005 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Cancel inspection per conversation with Wayne.
|
INSP-Sprinkler Rough-in/Hydro | 9/7/2005 | 9/8/2005 | 9/12/2005 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry Cancel inspection per conversation with Wayne.
|
Issue and Print Permit | | | 2/23/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 2/9/2005 | | 2/18/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/18/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/18/2005 | | 2/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/18/2005 | | DONE |
|
|
|
|
Application received | | | 2/9/2005 | | |
|
|
|
|