Permit Number | FIR05-00096 |
Status | Finaled |
Name |
MICRON TECHNOLOGY INC FA
|
Site Address |
8000 S FEDERAL WAY
|
Project Name | alm - BLDG 17C |
Customer Number | 8028 |
ePlanReview | |
Description |
To demo one 15/75 cd H/S and provide total notification (3 appliances) in the remodeled space in building 17C. The 75 cd ceiling mounted strobe appears to implement the "Spacing in Rooms" (as per NFPA 72, 7.5.4.2.4 for corridors 20' or less in width) and appears to provide the appropriate coverage. It appears the calcs (battery and voltage drop) have sufficient capacity. No comments have been written, PDS Fire Inspector to field verify.
BLD05-00314 for Micron Building #17C - Stock/Compensation Remodel Room #125A (17C-20048028) - To install approximately 100 lineal feet of interior partitions and four interior entry doors and side lights to create three new 80 square foot office spaces along the west wall of open office Stock #125A and a new 115 square foot Conference Room #125G at the south end of open office area #125A, as well as, infill an opening with a door and partition wall to enclose Storage #125H. This permit also includes the removal of the east interior wall installation of a side light at the north wall to convert Conference Room #125C to Office #125F. This permit also includes related ceiling grid, mechanical and electrical work. This alteration is being done on the first floor of Building #17C between grid lines 8.1&9.1 and H&J. All construction per the approved plans and red lined notes. JCM
|