Permit Information
Permit NumberFIR05-00099
StatusFinaled
Name PROTEX
Site Address 3101 W MAIN ST
Project Namealm - RIVERFRONT PLAZA LLC
Customer Number 
ePlanReview 
Description
To provide a manual fire alarm system in the shell and core areas only at this time. The required manual fire alarm system includes HVAC shutdown, elevator recall/shutdown and notification throughout.

6/22/2005 - Additional Scope: First floor main doors (shown with a mag lock) will have door release (per IFC 1008.1.3.4) and in-duct smoke detectors to control fire/smoke dampers (located on the second floor) have been added to the manual fire alarm system.

The associated building permit (BLD 04-01429) is to construct a new 21,680 square foot, two story, office shell and core building and related site improvements. This building is constructed concrete tilt-up exterior wall, and steel structural frame with steel floor joists and roof trusses. The core work to be completed under this permit include the stairways, elevator and machine room, first floor lobby, restrooms and electrical room and second floor lobby, restrooms and nonrated corridor. This building is fully fire sprinklered, the sprinklers are used for area increase. First Fl: 11,120 sq. ft., Second Fl: 10,560 sq. ft.. All construction per the approved plans and attached comment list. #04-414/JCM Riverfront Plaza (Office Building Shell & Core) -

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/15/20057/15/20057/15/2005PPASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection7/6/20057/7/20057/7/2005AFAIL
DetailsForrest France
Provide sign at FACP door and fire riser door, provide hd cut sheet, provide lock and label at FACP breaker, verify mag lock function on main doors when installed, provide list of signal verification from central station, provide device location map at panel.
(F) Reprint permit  7/6/2005 DONE
CHANGE STATUS TO (ISS)  7/6/2005 DONE
Inspection Record Card- Fire7/6/2005 7/6/2005 DONE
Alarm Plan Check  6/22/2005 PASS
Plan Modification. Approved pending PDS Fire Inspector field verification.
PLANS/APPL TAKEN TO FRONT DESK  6/22/2005 DONE
Permit Ready to Issue  6/22/2005 DONE
Telephone call  6/22/2005 DONE
lft ms with receptionist for rob ###-#### that permit and fees are ready to picked up
Case Summary  6/16/2005 DONE
CHANGE STATUS TO (ISS)  3/23/2005 DONE
issued permit
Inspection Record Card- Fire3/22/2005 3/22/2005 DONE
Plan assigned to (Mary)2/18/2005 3/22/2005 DONE
Alarm Plan Check  3/22/2005 PASS
Approved pending PDS Fire Inspector field verification.
PLANS/APPL TAKEN TO FRONT DESK  3/22/2005 DONE
Telephone call  3/22/2005  
left mess that permit is ready
Permit Ready to Issue  3/22/2005  
Case Summary  3/21/2005  
Plan resubmittals received  3/16/2005 DONE
Alarm Plan Check  3/3/2005 FAIL
Resubmittal required. Spoke with Jim Mesplay (Apex, PE) regarding the notification appliances in the stairwells, insufficient coverage in the riser room and a smoke detector in the elevator hoistway. I told him that some of the other issues I would take up with Protex. He agreed to no written comments.
Telephone call  3/3/2005 DONE
Spoke with Rob Ahten (Protex) regarding the submittal. I requested a site plan that includes the streets, waterflows should be annunciated separately (addressable panel) and the permit application needs to be filled out correctly. A resubmittal is required. No comments written.
Application received  2/18/2005  