INSP-Final Inspection | 7/15/2005 | 7/15/2005 | 7/15/2005 | P | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
INSP-Final Inspection | 7/6/2005 | 7/7/2005 | 7/7/2005 | A | FAIL |
Forrest France
|
|
|
Provide sign at FACP door and fire riser door, provide hd cut sheet, provide lock and label at FACP breaker, verify mag lock function on main doors when installed, provide list of signal verification from central station, provide device location map at panel.
|
(F) Reprint permit | | | 7/6/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/6/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/6/2005 | | 7/6/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/22/2005 | | PASS |
|
|
|
Plan Modification. Approved pending PDS Fire Inspector field verification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/22/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/22/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/22/2005 | | DONE |
|
|
|
lft ms with receptionist for rob ###-#### that permit and fees are ready to picked up
|
Case Summary | | | 6/16/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/23/2005 | | DONE |
|
|
|
issued permit
|
Inspection Record Card- Fire | 3/22/2005 | | 3/22/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 2/18/2005 | | 3/22/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/22/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/22/2005 | | DONE |
|
|
|
|
Telephone call | | | 3/22/2005 | | |
|
|
|
left mess that permit is ready
|
Permit Ready to Issue | | | 3/22/2005 | | |
|
|
|
|
Case Summary | | | 3/21/2005 | | |
|
|
|
|
Plan resubmittals received | | | 3/16/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/3/2005 | | FAIL |
|
|
|
Resubmittal required. Spoke with Jim Mesplay (Apex, PE) regarding the notification appliances in the stairwells, insufficient coverage in the riser room and a smoke detector in the elevator hoistway. I told him that some of the other issues I would take up with Protex. He agreed to no written comments.
|
Telephone call | | | 3/3/2005 | | DONE |
|
|
|
Spoke with Rob Ahten (Protex) regarding the submittal. I requested a site plan that includes the streets, waterflows should be annunciated separately (addressable panel) and the permit application needs to be filled out correctly. A resubmittal is required. No comments written.
|
Application received | | | 2/18/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 3/22/2005 | | | | |
|
|
|
|