Permit Information
Permit NumberFIR05-00108
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 12400 W MCMILLAN RD
Project Namealm - CENTENNIAL HIGH SCHOOL
Customer Number901555501
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, required automatic detection and notification (voice/evac) throughout the A3 occupancy and horn/strobe notification in the E occupancy. (1 hour fire area separation wall exists at column line D.)

The associated building permit (BLD 04-01188) is to construct a 32,606 sq. ft. one story, Type II-B fully fire sprinklered theater / classroom building. Other work includes all site improvements, paving and landscaping per approved plans and attachments, cup04-0002. Fire sprinklers are used for area. Building to have fire alarm system for theater with more than 1000 occupants and for group E area in accordance with Chapter 9 IBC as regulated by the Fire Dept.- **CENTENNIAL HIGH SCHOOL PERFORMING ARTS CENTER**

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20061/19/20061/19/2006APASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Final Inspection1/13/20061/18/20061/18/2006PPART
DetailsTroy Cobbley
Still need to finish with the duct smoke detectors, verify cd of av's and spacing and verify signals.
Permit Ready to Issue  12/29/2005 DONE
Inspection Record Card- Fire12/29/2005 12/29/2005 DONE
Telephone call  12/29/2005 DONE
Spoke with Charlie & told him that permit is ready & fees///12/29/05 @8:10am BAS
Issue and Print Permit  12/29/2005 DONE
Alarm Plan Check  12/28/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/28/2005 DONE
Plan assigned to (Mary)2/24/2005 12/28/2005 DONE
Plan resubmittals received  12/15/2005 DONE
Alarm Plan Check  11/10/2005 FAIL
Resubmittal required. This submittal does not include the "approved" design from George Eidam for the 10' stage roll-up door smoke detection. I phoned Charlie and advised him that he would need to resubmit.
Plan resubmittals received  10/31/2005 DONE
Case Summary  10/31/2005 DONE
INSP-Conference9/13/20059/14/20059/14/2005ACANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 9/13/2005 at 11:34:59 AM. Contact: ###-####.
FIR-Aging Inspection9/5/20059/5/20059/12/2005 NR
DetailsTroy Cobbley
work is in progress
Issue and Print Permit  5/24/2005 DONE
Inspection Record Card- Fire5/20/2005 5/20/2005 DONE
Telephone call  5/20/2005 DONE
called told chris permit is ready and no fees
Permit Ready to Issue  5/20/2005 DONE
Alarm Plan Check  5/20/2005 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  5/19/2005 DONE
Drawings have an additional revision that refers to "addendum changes". I have requested from Ronnie Zahm the scope of the addendum changes. He will e-mail it to me.
Plan resubmittals received  5/16/2005 DONE
Case Summary  5/16/2005 DONE
Alarm Plan Check  3/10/2005 FAIL
Resubmittal required. Faxed comments to Chris Willis.
Miscellaneous action  3/8/2005 DONE
Received a fax from George Eidam that the information was included on A0.02 sheet and I should be able to get it internally. Sam and I reviewed the requirements and there is a one-hour fire separation wall between the stage and the hallway (Column line D)
Telephone call  3/7/2005 DONE
Request to Chris WIllis to explain why the voice/evac was only being installed in one area in lieu of the entire building. (no fire separation areas were indicated on the FA permit plans)
Application received  2/24/2005