INSP-Final Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled, sufficient flow has been verified through the system backflow preventer.
|
INSP-Final Inspection | 7/21/2005 | 7/22/2005 | 7/22/2005 | A | FAIL |
Forrest France
|
|
|
Foreward flow test failed to produce required gpm.
|
INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 | A | FAIL |
Forrest France
|
|
|
Provide foreward flow test of backflow preventer, provide NFPA25, attatch calc. sticker, install missing escutcheon at riser room, sinage to indicate areas controled by system control valves.
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Forrest France
|
|
|
Need lateral EQ brace installed on the last piece of main 2nd floor SW side per NFPA 13 9.3.5.3.4, attatch retaining straps in two locations 2nd floor, missing hangers on penthouse branch line supply, provide guages at floor control manifolds as shown on approved plans.
|
INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of 2nd and 3rd floor shell pipe passed.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2005 | 7/5/2005 | 7/5/2005 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 3:34:44 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 5 2005 7:10AM.
|
INSP-Sprinkler Rough-in/Hydro | 6/21/2005 | 6/23/2005 | 6/23/2005 | A | FAIL |
Forrest France
|
|
|
Shell area first floor needs hanger at 1" arm over, head cage in elevator pit, SW is blocked in electrical room, inadequate coverage at bottom stair landings. 2nd and 3rd floor shell piping not ready for inspection.
|
INSP-Sprinkler Rough-in/Hydro | 6/23/2005 | 6/23/2005 | 6/23/2005 | P | PART |
Forrest France
|
|
|
Standpipe and overhead hydro test of first floor piping OK.
|
Sprinkler Plan Check | 3/31/2005 | | 4/1/2005 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 4/1/2005 | | DONE |
Bill Alexander
|
|
|
Took modified plasn to the permit desk for calling and returning.
|
Inspection Record Card- Fire | 4/1/2005 | | 4/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 4/1/2005 | | DONE |
|
|
|
lft mes with sec ###-#### that permit and no fees are readyto be picked up
|
Issue and Print Permit | | | 3/31/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/31/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/25/2005 | | 3/24/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/14/2005 | | 3/24/2005 | | PART |
Bill Alexander
|
|
|
1. Plans are incomplete. This facility is incorporating a Class I, Manual Combination, Wet Standpipe System.
a. Standpipe system calculations are required at a minimum residual pressure of 100 psi at the outlet of the hydraulically most remote 2½" hose connection flowing 500-gpm (250 gpm at the two hydraulically most remote hose connections on the standpipe) and 250-gpm for the other stairs (this building) with the calculation procedures in accordance with 7.10.1.2.
i. Branch lines shall be sized based on the hydraulic criteria established in Section 7.8 and Section 7.10 but not less than 2½".
ii. Where a standpipe system is provided with a fire department connection, the authority having jurisdiction shall be consulted regarding the water supply available from a fire department pumper per 7.7.4. Fire department pumper information at the point of connection shall be obtained from the Fire Marshal by contacting Jerry Prinzing @ ###-####.
iii. Address and provide a sign which indicates the pressure required at the inlets to deliver the (standpipe) system demand at a minimum residual pressure of 100 psi at the outlet of the hydraulically most remote 2½" hose connection flowing 500-gpm (250 gpm at the two hydraulically most remote hose connections on the standpipe) and 250-gpm for the other stairs with the calculation procedures in accordance with 7.10.1.2.
(NFPA 14-7.8, 7.10, 6.3.5.2.2)
March 23, 2005 - Calculations are flawed. NFPA 14-7.10.1.2* Hydraulic Calculation Procedure. Review your calculations and include correct locations of hoses flowing, etc. Your calculations also show node 22 as a hose flowing?
7.10.1.2.1 Hydraulic calculations and pipe sizes for each standpipe shall be based on providing 250 gpm at the two hydraulically most remote hose connections on the standpipe and at the topmost outlet of each of the other standpipes at the minimum residual pressure required by Section 7.8.
Revise and resubmit correct calculations for system design verification.
Sign requirements are addressed in the code and anything less than what is addressed in the code is to be approved by the acting Fire Marshal or the Fire Chief, (in written approval). Signage requirements are also addressed in items #39, 53, 101 below.
NOTE: Fire Department pumper water supply shall be designed to include a 150 psi @ 1,500 gpm and no more, (unless approval is provided in writing from the Fire Chief).
2. Regarding earthquaking, provide supports restraints above the lowest level where flexible fittings are used. Revise and resubmit corrected plans. Supports above the lowest level shall also restrain the pipe to prevent movement by an upward thrust where flexible fittings are used. (NFPA 13:9.2.5.3.2, BMC 7-01-50-901.2, IFC 105.4.2)
March 23, 2005 - Not provided. Include this requirement on the plans.
3. Backflow prevention is not provided or addressed with required forward flow components/provisions. Provide/address forward flow provisions test and appurtenance in accordance with NFPA 13-8.16.4.6.1*. (BMC 7-01-50-901.2, IFC 105.4.2)
March 23, 2005 - Unacceptable configuration. Your system design will require the following process:
a. Deactivation shutdown,
b. Draining,
c. Pipe installation,
d. Flow testing,
e. Shutdown,
f. Draining,
g. Removal of pipe,
h. Reactivation.
Provide a configuration of piping and appurtenance that will not require system/s shutdown for required forward flow testing of backflows, thus eliminating requirements and policing of IFC 901.7.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/24/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/24/2005 | | 3/24/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/24/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/14/2005 | | |
|
|
|
|
Sprinkler Plan Check | 2/25/2005 | | 3/3/2005 | | FAIL |
Bill Alexander
|
|
|
The data has been moved to a Word document attached to this case.
|
Miscellaneous action | | | 3/3/2005 | | DONE |
|
|
|
Took failed review documents/plans to permit desk for calling and returning for corrections.
|
Telephone call | | | 3/3/2005 | | DONE |
|
|
|
tlk to steven johnson that his permit that failed is ready to be picked up
|
Application received | | | 2/25/2005 | | |
|
|
|
|