Permit NumberFIR05-00114
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 277 N MILWAUKEE ST
Project NameSPR VANILLA TARGET RETAIL "E"
Customer Number 
ePlanReview 
Description
(VANILLA FINISH)(TARGET RETAIL "E"-WESTPARK TOWNE PLAZA) To add 6 and relocate 10 existing fire sprinklers for the creation of a 1,500-ft/2 vanilla finish area with a one restroom. This building is fully fire sprinklered for area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02410.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/17/20053/17/20053/17/2005PFAIL
DetailsTroy Cobbley
INSP-Final Inspection3/17/20053/17/20053/17/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
DOC - Permit Finaled3/17/20053/17/20053/17/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/17/2005 3:36:48 PM
Issue and Print Permit  3/7/2005 DONE
Plan assigned to (Bill)2/25/2005 3/4/2005 DONE
DetailsBill Alexander
Sprinkler Plan Check2/25/2005 3/4/2005 PART
DetailsBill Alexander
1. It appears with the installation of the new tenant demising wall on the west side of this tenant space is affecting fire sprinklers above (and possibly below) areas outside this permitted work area. Review, revise and resubmit required changes in all areas this vanilla finish will affect the buildings fire sprinkler systems protection. (BMC 7-01-50-901.2, IFC 105.4.2)

2. Fire sprinkler data submittals provided have multiple fire sprinklers addressed. Please address which fire sprinkler incorporating by annotation and include the escutcheon. (BMC 7-01-50-901.2, IFC 105.4.2)

3. TJI's were used in this facility. These trusses have specific attachment requirements for pipe and earthquake attachments. Provide correct listed installation requirements as established by the manufacturer along with the related appurtenance this contractor is incorporating in this permit request on the plans for installation code verification. (BMC 7-01-50-901.2, IFC 105.4.2)
PLANS/APPL TAKEN TO FRONT DESK  3/4/2005 DONE
Inspection Record Card- Fire3/4/2005 3/4/2005 DONE
Permit Ready to Issue  3/4/2005 DONE
Application received  2/25/2005