INSP-Final Inspection | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | FAIL |
Troy Cobbley
|
|
|
|
INSP-Final Inspection | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler finaled
|
DOC - Permit Finaled | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/17/2005 3:36:48 PM
|
Issue and Print Permit | | | 3/7/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/25/2005 | | 3/4/2005 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/25/2005 | | 3/4/2005 | | PART |
Bill Alexander
|
|
|
1. It appears with the installation of the new tenant demising wall on the west side of this tenant space is affecting fire sprinklers above (and possibly below) areas outside this permitted work area. Review, revise and resubmit required changes in all areas this vanilla finish will affect the buildings fire sprinkler systems protection. (BMC 7-01-50-901.2, IFC 105.4.2)
2. Fire sprinkler data submittals provided have multiple fire sprinklers addressed. Please address which fire sprinkler incorporating by annotation and include the escutcheon. (BMC 7-01-50-901.2, IFC 105.4.2)
3. TJI's were used in this facility. These trusses have specific attachment requirements for pipe and earthquake attachments. Provide correct listed installation requirements as established by the manufacturer along with the related appurtenance this contractor is incorporating in this permit request on the plans for installation code verification. (BMC 7-01-50-901.2, IFC 105.4.2)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/4/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/4/2005 | | 3/4/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/4/2005 | | DONE |
|
|
|
|
Application received | | | 2/25/2005 | | |
|
|
|
|