Information based on query as of Sunday, October 4, 2026.
Permit Information
Permit NumberFIR05-00126
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 347 N MILWAUKEE ST
Project NameSPR THE VITAMIN SHOPPE
Customer Number 
ePlanReview 
Description
(THE VITAMIN SHOPPE) To install 35 new pendant fire sprinkler heads in the remodel an existing 5,003-ft/2 building, for a new retail tenant. The fire sprinkler work is related to miscellaneous interior demolition work, a new interior wall and new suspended ceiling. This building is fully fire sprinklered to allow a non-rated exit corridor. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02926.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/15/20054/15/20054/15/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Final Inspection4/5/20054/5/20054/5/2005PPART
DetailsForrest France
###-#### - john Sprinkler rough in ok to cover.
Permit Ready to Issue  4/5/2005 DONE
Telephone call  4/5/2005 DONE
tlk to john warnick ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  4/5/2005 DONE
Plan assigned to (Bill)3/24/2005 4/4/2005 DONE
DetailsBill Alexander
Sprinkler Plan Check3/24/2005 4/4/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/4/2005 DONE
INSP-Sprinkler Rough-in/Hydro3/28/20053/28/20053/28/2005PFAIL
DetailsTroy Cobbley
Could not do inspection since resubmittals are required for plans 3/28/2005 4:01:58 PM
Plan resubmittals received  3/24/2005 DONE
Issue and Print Permit  3/22/2005 DONE
Inspection Record Card- Fire3/21/2005 3/21/2005 DONE
Permit Ready to Issue  3/21/2005 DONE
Plan assigned to (Bill)3/4/2005 3/18/2005 DONE
Sprinkler Plan Check3/4/2005 3/18/2005 PART
DetailsBill Alexander
1. Plan is incomplete. Provide a "vicinity", "site" plan. (BMC 7-01-50-901.2, IFC 105.4.2)

2. Plan is incomplete. Provide all room/area hazard identification/use in this permit work scope on the plans. (BMC 7-01-50-901.2, IFC 105.4.2)

3. Plan is incomplete. Provide all pertinent detail information for all systems, construction items and related which affect fire sprinkler layout/location and spacing on the plans. Include any elevation views that may help clarify meeting minimum fire code verification on the plans. This includes HVAC registers, soffits, surface mounted light fixtures and similar. (BMC 7-01-50-901.2, IFC 105.4.2)

4. Plan is incomplete. Provide hanger information incorporating and include the listed attaching device/s and its connection/s to the structure in detail on the plan. (BMC 7-01-50-901.2, IFC 105.4.2)

5. Plan is incomplete. Clarify any storage area walls and the construction information relating. The designer indicates that all cavity fire sprinklers will be removed. All open ceiling walls must be installed to the roof, meeting construction separation requirements for the hazard separating or sprinklers will be required throughout all (open) cavities. (NFPA 13-4.1, 8.14.1, 3.3.14, 3.3.16, BMC 7-01-50-901.2, IFC 105.4.2)

6. Plan is incomplete. Provide existing riser information which shall include required outside control, , forward flow connections/piping for backflow testing and related. If none are provided, then make necessary changes and include them on the plan. (BMC 7-01-50-901.2, IFC 105.4.2)

7. This building was originally constructed in 1994/1995 and the applicable building code was the 1991 UBC. Building use has always been retail. The current building Type of Construction is V-B and it is fully fire sprinklered to allow a non-rated exit corridor. The exit corridor that serves the second exit from the retail sales floor will be downgraded to a non-rated corridor per the applicant under this permit. (Fully sprinklered M Occupancy) Provide quick response fire sprinklers in the exist corridor in meeting with the allowance and include it on the plan. (BMC 7-01-50-901.2, IFC 105.4.2)
PLANS/APPL TAKEN TO FRONT DESK  3/18/2005 DONE
Case Summary  3/4/2005 DONE
Application received  3/4/2005