Permit Information
Permit NumberFIR05-00128
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project NameALM - ST LUKES
Customer NumberGROUND FLOOR
ePlanReview 
Description
To install a new FACP (18) and relocate one NAC extender panel from the ground floor to the basement (communication room) to prepare for a large remodel that is associated with BLD04-02203. The new FACP will monitor two existing SLC loops (SLC-01 sub-basement; from FACP-02-SLC-0-1 and SLC-02, east mechanical basement, from FACP-06-SLC-01). The NAC panel is being relocated ~ 10 feet down one floor to the same space. The same notification circuits will be extended and re-connected. (NAC-1, NAC-8, NAC-9 and NAC-10 all located in the sub-basement). There are no plans with this permit, just a riser diagram. The building maps will be furnished at the time of inspection to afford locations of the affected circuits. The PDS Fire Inspector shall field verify functionality of the SLCs and the extended NAC circuits. No written comments. The battery and voltage drop calculations appear adequate.

There is no associated building permit.



Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/11/20112/14/20112/14/2011APASS
DetailsForrest France
Permit finaled.
FIR-Aging Inspection2/11/20112/11/20112/11/2011 PASS
DetailsForrest France
FIR-Aging Inspection12/3/201012/3/201012/8/2010 PASS
DetailsForrest France
Permit final okay- work completed.
FIR-Aging Inspection9/3/20109/3/20109/10/2010 FAIL
DetailsForrest France
DOC - Permit Finaled5/12/20105/12/20105/13/2010PDONE
DetailsForrest France
FIR-Aging Inspection5/12/20105/12/20105/12/2010 DONE
DetailsForrest France
FIR-Aging Inspection4/14/20064/14/20064/20/2006 DONE
DetailsForrest France
Spoke to the alarm contractor who said the project is not yet completed and still in progress due to a phased remodel.
Plan assigned to (Mary)3/7/2005 3/11/2005 DONE
Alarm Plan Check  3/11/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  3/11/2005 DONE
Inspection Record Card- Fire3/11/2005 3/11/2005 DONE
Permit Ready to Issue  3/11/2005 DONE
Telephone call  3/11/2005 DONE
lft vm with john shilton ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  3/11/2005 DONE
Application received  3/7/2005