INSP-Final Inspection | 8/9/2005 | 8/9/2005 | 8/9/2005 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler permit finaled
|
INSP-Supply line flush | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Troy Cobbley
|
|
|
Supply line flush passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/1/2005 | 4/1/2005 | 4/1/2005 | P | PASS |
Forrest France
|
|
|
Overhead rough in ok to cover.
|
Inspection Record Card- Fire | 4/1/2005 | | 4/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 4/1/2005 | | DONE |
|
|
|
Spoke with Jeff and told him that permit is ready & no fees due///4/1/05 9:30am BAS
|
Sprinkler Plan Check | 4/1/2005 | | 4/1/2005 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 4/1/2005 | | DONE |
|
|
|
Took resubmittals to permit desk for calling and releasing.2nd review-no fee.
|
Plan resubmittals received | | | 3/29/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/25/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/7/2005 | | 3/22/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/7/2005 | | 3/22/2005 | | PART |
Bill Alexander
|
|
|
1. Fire sprinkler riser closet is considered a "mechanical room" and shall be protected by fire sprinkler protection. Provide and show protection meeting requirements of NFPA 13D-8.6 and 17.5.
2. Backflow preventer identified on the plans is an "Ames" and the data submittal provided is a "Watts"? Clarify and provide correct/correlating information for calculation pressure loss verification. (IFC 104.9, 105.4.2, 901.2)
3. Hydraulic calculations verification for the Main Floor Area, 2 sprinkler heads testing are flawed. The Reliable Model "F3QR", Q.R., Dry HSW 5.6 K-factor (½"), R5734 is a ½" orifice sprinkler with an average 5.6 K-factor rating. Provide revised calc verification for this test and resubmit. (IFC 104.9, 105.4.2, 901.2)
4. Provide data submittals on the Reliable Model "F3QR", Q.R., Dry HSW 5.6 K-factor (½"), R5734. (IFC 104.9, 105.4.2, 901.2)
5. Unless the Laundry room has a ceiling to floor cabinet, the sprinkler head is not protecting all walls (shadowed). Provide clarification of construction. (IFC 104.9, 105.4.2, 901.2)
6. The domestic control shall be connected upstream of the fire sprinkler take-off, (no exceptions). Provide plans the address this requirement. (NFPA 13D-6.2, A.6.2[a], A.6.3[a], IFC 901.2, IFC 105.4.2).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/22/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/22/2005 | | 3/22/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/22/2005 | | |
|
|
|
|
Telephone call | | | 3/22/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 3/7/2005 | | |
|
|
|
|