Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR05-00134
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 12040 W EXECUTIVE DR
Project Namealm - BUILDING
Customer Number 
ePlanReview 
Description
To provide duct detectors to an existing fire alarm system. The original fire alarm permit (FIR00-00653) has expired prior to completion and final inspection. Therefore, the entire system will be tested by the PDS Fire Inspector prior to occupancy of the building permits (see associated building permits below). The required sprinkler monitoring fire alarm system includes HVAC shutdown. (I have attached the comments from the original permit.)

An associated building permit (BLD 04-01686) is to remodel a 1,320 sq. open office area within the existing 53,424 sq.ft. fabrication facility to create three (3) private offices a foyer and open office area per approved plans. Work includes construction of approximately 90 feet of new partitions to divide up existing open space into offices and foyer. Note: This building was built in Ada County in 1997 and annexed into Boise City on 12/31/99. PC04-473/drs (BMC WEST-DOOR PLANT DIVISION) This building is fully sprinklered for allowable area increase. A "Letter of Compliance" is required as a condition of this permit.

An associated building permit (BLD 04-01487) is to obtain a Letter of Compliance at final approval of a remodel of a 170 sq. ft. area to create a private office within the existing 13,390 sq.ft. warehouse space, per approved plans. Work includes construction of interior non-bearing, non-combustible walls and access door to create office; new non-combustible ceiling joists with sheetrock on ceiling; mechanical, electrical, fire suppression modifications to provide for tenant needs and comply with current adopted codes and ordinances. Note: Area above new office was not submitted for or reviewed for any use above. NO STORAGE OR OCCUPANCY ALLOWED ABOVE OFFICE. This building was constructed in Ada County in 1997 and annexed into Boise on 12/31/99. PC04-423/drs (INLAND NORTHWEST DISTRIBUTING INC)

An associated building permit (BLD 04-02445) is to install 2 overhead doors and relocate a man door from office exterior to exterior on south side (front) of building per approved plans and CZC04-00175. Engineer has provided a letter stating that the openings have been analyzed and no additional structural modifications will be required, the existing structure is capable of supporting the new headers see letter from pinnacle engineering. (rmh) (FED EX)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  8/4/2005 DONE
INSP-Final Inspection4/4/20054/5/20054/5/2005APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection4/1/20054/4/20054/4/2005AFAIL
DetailsForrest France
Duct sampling tubes in two ducts need to be the correct length. Zones at alarm company need to be corrected.
Override - Parcel Holds1/1/19001/1/19004/4/2005  
final inspection
Override - Parcel Holds1/1/19001/1/19004/4/2005  
Override - Parcel Holds1/1/19001/1/19004/1/2005  
fire inspection
INSP-Final Inspection3/30/20053/30/20053/30/2005PFAIL
DetailsTroy Cobbley
Duct smoke detectors did not shut down hvac units. Need correct orfice in the inspectors test for proper testing. Provide knox key box per review note#10. Mount map at facp. Duct smoke detector zone is showing as vault alarm at the monitoring service. 3/30/2005 4:49:45 PM
Override - Parcel Holds1/1/19001/1/19003/30/2005  
fire inspection
Issue and Print Permit  3/16/2005 DONE
Plan assigned to (Mary)3/10/2005 3/15/2005 DONE
Alarm Plan Check  3/15/2005 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  3/15/2005 DONE
Chris Willis, the RTS to be supplied by the mechanical.
PLANS/APPL TAKEN TO FRONT DESK  3/15/2005 DONE
Permit Ready to Issue  3/15/2005 DONE
Telephone call  3/15/2005 DONE
Left voice message for Chris that permit is ready & fees///3/15/05 4:33pm BAS
Inspection Record Card- Fire3/15/2005 3/15/2005 DONE
Telephone call  3/14/2005 DONE
Plans and riser do not include the remote LEDs for the duct detectors (zoned). Left a message for Chris Willis (Simplex)
Application received  3/10/2005