DOC - Permit Finaled | | | 8/4/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
INSP-Final Inspection | 4/1/2005 | 4/4/2005 | 4/4/2005 | A | FAIL |
Forrest France
|
|
|
Duct sampling tubes in two ducts need to be the correct length. Zones at alarm company need to be corrected.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/4/2005 | | |
|
|
|
final inspection
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/4/2005 | | |
|
|
|
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/1/2005 | | |
|
|
|
fire inspection
|
INSP-Final Inspection | 3/30/2005 | 3/30/2005 | 3/30/2005 | P | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors did not shut down hvac units. Need correct orfice in the inspectors test for proper testing. Provide knox key box per review note#10. Mount map at facp. Duct smoke detector zone is showing as vault alarm at the monitoring service. 3/30/2005 4:49:45 PM
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 3/30/2005 | | |
|
|
|
fire inspection
|
Issue and Print Permit | | | 3/16/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 3/10/2005 | | 3/15/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/15/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Telephone call | | | 3/15/2005 | | DONE |
|
|
|
Chris Willis, the RTS to be supplied by the mechanical.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/15/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/15/2005 | | DONE |
|
|
|
|
Telephone call | | | 3/15/2005 | | DONE |
|
|
|
Left voice message for Chris that permit is ready & fees///3/15/05 4:33pm BAS
|
Inspection Record Card- Fire | 3/15/2005 | | 3/15/2005 | | DONE |
|
|
|
|
Telephone call | | | 3/14/2005 | | DONE |
|
|
|
Plans and riser do not include the remote LEDs for the duct detectors (zoned). Left a message for Chris Willis (Simplex)
|
Application received | | | 3/10/2005 | | |
|
|
|
|