Permit Information
Permit NumberFIR05-00141
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 800 E PARK BLVD Unit: 7TH FLR
Project NameMK PLAZA IV-7TH FLR
Customer Number 
ePlanReview 
Description
To provide complete notification to the remodeled area on the 7th floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, required automatic fire/smoke damper control, door release and notification throughout (voice evac is required as this is classified as a high rise).

The associated building permit (BLD 05-00102) is to remodel 7,283 sq.ft. of office area previously occupied by 3 tenants to merge into one tenant space per approved plans. Work includes selective demolition of interior non-bearing walls and portion of existing rated 1-hour corridor; to infill openings created by demo and install new 20 minute rated door assemblies for doors 700 & 724; upgrade electrical, sprinkler & fire alarm systems to meet tenant needs and comply with minimum adopted codes and ordinances. Architect has declared on Sheet A0.1 that there are to be no changes to building envelope, electrical or mechanical that would involve energy code compliance. No electrical or mechanical submitted as part of this permit. The building is fully sprinklered to meet high rise requirements and allowable area increase. drs- (COSHO HUMPHREY LLP)(MK PLAZA IV-STE 790)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing4/12/20054/12/20054/13/2005PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 4/12/2005 at 9:54:23 AM. Contact: ###-####.
INSP-Final Inspection4/13/20054/13/20054/13/2005PPASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Alarm Testing4/7/20054/8/20054/8/2005PFAIL
DetailsTroy Cobbley
Contact: ###-####. Two a/v's are mounted too high. Tested devices and they operated ok but will need to retest to verify the relocated two still operate
Issue and Print Permit  3/31/2005 DONE
Plan assigned to (Mary)3/15/2005 3/29/2005 DONE
Plan resubmittals received  3/29/2005 DONE
Received revised matrix and cutsheets for the sync module via fax.
Alarm Plan Check  3/29/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/29/2005 DONE
Case Summary  3/29/2005 DONE
Inspection Record Card- Fire3/29/2005 3/29/2005 DONE
Permit Ready to Issue  3/29/2005 DONE
Telephone call  3/29/2005 DONE
tlk to kevin ###-#### that permit and fees are ready to be picked up
Telephone call  3/28/2005 DONE
Phoned John Lopez at Fire Sentry to request a revised matrix and sync module cut sheets. He stated he would get them faxed right over.
Plan resubmittals received  3/25/2005  
received 2 additional sets of plans
Alarm Plan Check  3/23/2005 FAIL
No comments written. Resubmittal is required due to a synchronization of visual appliances in the space. John Lopez has been notified and will revise plans and calcs to reinsert into the existing submittals.
Application received  3/15/2005