Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR05-00143
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm - BLDG 26
Customer Number8119
ePlanReview 
Description
To provide total notification coverage for a remodeled space on the 2nd floor of BLDG 26. The existing required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout. The battery and voltage drop calculations appear to have sufficient capacity. No written comments, PDS Fire Inspector to field verify proper visual locations. An updated building map (showing the architectural changes) shall be provided at time of inspection.

The associated building permit BLD05-00592 is to remove all of the interior partitions and doors creating all of the offices that surround the Process Development #203A with the exception of Offices #203G, #203H and #203I at the south east corner. The removal of these offices creates a large, 6000 square foot, open area at Process Development #203A. To install new interior partitions and one new interior door as well as two new 8080 entry doors from Corridor #200C. The new partitions will create a new 375 sq. ft. C-SAM #203B area, a new 2230 sq. ft. QC/FA LAB #203A, a new 1325 sq. ft. INSPECTION LAB #203C and a new 1800 sq. ft. BULLPEN #203D. This permit also includes mechanical, electrical, suspended ceiling, flooring, fire alarms and fire sprinklers modifications associated with this remodel. This work is being done at the southeast corner of the second floor of Building #26 between grid lines #J&#M and #!12. All of the rated corridors, first and second floors, must be maintained because of long travel distances. All construction per the approved plans on file. JCM- Micron Building #26 - Complete QC/FA Inspection Labs in Area "C" - (#26-20058119) *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/26/20055/27/20055/27/2005APASS
DetailsTroy Cobbley
Fire alarm permit finaled. I had the fire alarm guys change a 30cd ceiling mount a/v in the lab area to a 95 to meet nfpa 72 spacing requirements. The location of the EOL was also changed.
INSP-Final Inspection4/22/20054/25/20054/25/2005PPART
DetailsTroy Cobbley
Office area is ok to occupy
INSP-Conference4/19/20054/20/20054/20/2005PFAIL
DetailsTroy Cobbley
Inspection was for an ok to occupy just the office area. Fire alarm system horns would not operate. I requested that system be tested prior to me inspecting.
Plan assigned to (Mary)3/16/2005 3/22/2005 DONE
Alarm Plan Check  3/22/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  3/22/2005 DONE
Inspection Record Card- Fire3/22/2005 3/22/2005 DONE
Permit Ready to Issue  3/22/2005  
Telephone call  3/22/2005 DONE
e-mailed that permit is ready
Issue and Print Permit  3/22/2005 DONE
Case Summary  3/16/2005  
Application received  3/16/2005