Permit Information
Permit NumberFIR05-00144
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3730 W QUAIL HOLLOW DR
Project NameSPR HEATHER RISE RESIDENCE
Customer NumberSEE COMMENTS
ePlanReview 
Description
HEATHER RICE RESIDENCE * To install a life safety, NFPA 13-D Modified, fire sprinkler system in a new five bedroom, two and half bathroom, 3,848-ft/2, two story single family dwelling (2700-ft/2 first floor/1148-ft/2 second floor) with an attached 798-ft/2 two car garage which requires barrier protection on all living space walls. The sprinkler flow alarm shall be attached to the residence smoke detection system. This NFPA 13D system shall be equipped with an alarm initiating device, commonly referred to as a flow switch, and an outside alarm indicating device. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-00107.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/7/20057/8/20057/8/2005PPASS
DetailsTroy Cobbley
Fire sprinklers finaled
INSP-Supply line flush7/6/20057/7/20057/7/2005PPASS
DetailsTroy Cobbley
Underground flush passed. Canopies have been installed on pendants.
INSP-Sprinkler Rough-in4/12/20054/13/20054/13/2005APASS
DetailsForrest France
Sprinkler rough-in overhead OK to cover.
INSP-Sprinkler Rough-in4/7/20054/8/20054/8/2005AFAIL
DetailsTroy Cobbley
Water meter is the wrong size. Pipe sizing and routing still does not match approved plans. Resubmit plans or fix. Re-inspection fees are being applied to this permit. Riser on plans is shown as steel but is installed as half plastic. Meet code for expose
Sprinkler Plan Check4/1/2005 4/7/2005 PASS
DetailsBill Alexander
Telephone call  4/7/2005 DONE
left mess that permit is ready
INSP-Sprinkler Rough-in/Hydro3/31/20054/1/20054/1/2005AFAIL
DetailsForrest France
Resubmit plans, piping installation does not match plans. Do not cover piping..
Plan resubmittals received  4/1/2005 DONE
Plan assigned to (Bill)3/16/2005 3/25/2005 DONE
DetailsBill Alexander
Sprinkler Plan Check3/16/2005 3/25/2005 PART
DetailsBill Alexander
1. Calculations are flawed. Meter shown 1" and calculated for a 2". Revise and resubmit. (IFC 105.2, 601.2)

2. Calculations are flawed. Underground supply from meter to system takeoff is shown 1¼" and calculated for a 2". Revise and resubmit. (IFC 105.2, 601.2)

3. Plans are incomplete, since reviewer cannot follow calculations. Provide correct and correlating hydraulic node points on the underground and through the riser that match the calculations provided. (IFC 105.2, 901.2 and BMC 7-01-50-901.2)

4. Provide and show on the plans a domestic control connected upstream of the fire sprinkler take-off, which shall be included in the calcs for system control. No other domestic shutoff can be installed upstream of this valve. No exceptions allowed for the location. (NFPA 13D-A.6.2[a], A.6.3[a] BMC 7-01-50, IFC 901.2, IFC 105.4.2, 105.2, IFC 105.2, 901.2 and BMC 7-01-50-901.2)


5. Plans provided show no terrain elevations. The calcs show a 4'-6" elevation change from the street tap to the top of the backflow? This permit approval is based on a design with the supply entering this facility on a level or downhill terrain. Water supplied uphill will require corrected calculations. Field Fire/Life Safety Inspector shall verify. (, IFC 105.2, 901.2 and BMC 7-01-50-901.2)

6. No light fixtures or fan location, etc. provided on the plans. These items clearly interfere with correct sprinkler density distribution with residential sprinkler installations. Fire testing has proven the requirement of wetting walls in the area protected by residential sprinklers at a level closer to the ceiling than that accomplished by standard sprinkler distribution. Where beams, light fixtures, sloped ceilings, and other obstructions occur, additional residential sprinklers are necessary to achieve proper response and distribution. In addition, for sloped ceilings, higher flow rates could be needed. Guidance should be obtained from the manufacturer. Reference NFPA 13D-7.5.5.3*. (IFC 105.2, 901.2 and BMC 7-01-50-901.2)

7. Second floor Utility Room requires head adjustment to wet walls in the area protected by residential sprinkler. Provide coverage on the plans. (NFPA 13D-8.6, IFC 105.2, 901.2 and BMC 7-01-50-901.2)

8. Provide data submittals for the 1½" Central riser manifold. (IFC 105.2, 901.2 and BMC 7-01-50-901.2)

9. Provide location of outside alarm indicating device which will be connected to the flow switch. (BMC 903.3.1.3.1, IFC 105.2, 901.2 and BMC 7-01-50-901.2)

10. Plan 2 of 2 has the hydraulic summery addressing the wrong floor? Revise and resubmit. (IFC 105.2, 901.2 and BMC 7-01-50-901.2)
PLANS/APPL TAKEN TO FRONT DESK  3/25/2005 DONE
Inspection Record Card- Fire3/25/2005 3/25/2005 DONE
Permit Ready to Issue  3/25/2005 DONE
Issue and Print Permit  3/25/2005 DONE
Application received  3/16/2005