Permit Information
Permit NumberFIR05-00150
StatusFinaled
Name PROTEX
Site Address 500 W BROAD ST
Project Namealm -500 BROAD STREET BLDG
Customer Number 
ePlanReview 
Description
To provide security door release upon fire alarm signal. The existing required sprinkler monitoring fire alarm system includes HVAC shutdown. The plans indicate the four (4) main entrance doors (two (2) north and two (2) south) have outfitted with access controlled egress. These doors must comply with the functionality as required in the IFC 1003.3.1.3.4. The battery calculation appears to have sufficient capacity. No written comments, PDS Fire Inspector to field verify proper functionality of the releasing of the security mag locks. An updated building map shall be provided at time of inspection.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/19/20054/19/20054/19/2005PPASS
DetailsForrest France
Fire alarm finaled. Mag door locks operated properly under test conditions.
INSP-Final Inspection4/15/20054/18/20054/18/2005APASS
DetailsForrest France
Life safety finaled. Mag door locks operated properly under test conditions.
Issue and Print Permit  4/15/2005 DONE
Alarm Plan Check  3/23/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
Plan resubmittals received  3/23/2005 DONE
Received revised matrix via fax.
PLANS/APPL TAKEN TO FRONT DESK  3/23/2005 DONE
Permit Ready to Issue  3/23/2005 DONE
Inspection Record Card- Fire3/23/2005 3/23/2005 DONE
Telephone call  3/23/2005 DONE
Spoke with Rob and told him that permit is ready & fees////3/23/05 8:05am BAS
Miscellaneous action  3/22/2005 DONE
Requested revised matrix to define the proper FA control of the security doors.
Application received  3/18/2005  
(F) Reprint permit  3/18/2005  
Plan assigned to (Mary)3/18/2005