INSP-Final Inspection | 5/27/2005 | 5/27/2005 | 5/27/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler finaled.
|
INSP-Final Inspection | 4/27/2005 | 4/29/2005 | 4/29/2005 | P | FAIL |
Troy Cobbley
|
|
|
Can't give final ok until ceiling tile has been installed at the sprinkler pendants. Sprinkler piping is ok to cover.
|
Telephone call | | | 4/21/2005 | | DONE |
|
|
|
customer picked up plans from simplex grinnell
|
Telephone call | | | 4/19/2005 | | DONE |
|
|
|
left mess for tom easton that permit is ready
|
Sprinkler Plan Check | 4/7/2005 | | 4/18/2005 | | PASS |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in | 4/6/2005 | 4/7/2005 | 4/7/2005 | A | PART |
Forrest France
|
|
|
Ok to cover elevator lobby only. Resubmittals required per review comments
|
Plan resubmittals received | | | 4/7/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/6/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/22/2005 | | 3/31/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/22/2005 | | 3/31/2005 | | PART |
Bill Alexander
|
|
|
1. Plan is too vague and incomplete in relaying actual scope of work. Address the following for clarification:
a. Sprinkler head legend does not correlate with scope of work on the plans. Symbols don't correlate.
b. Provide clearer details as to what is new, what is relocated and what are being replaced in the related building permit work.
c. No areas are identified in the related building permit work area
d. Several lines adding are not sized, and if they are, the reviewer cannot clearly identify them.
e. Provide data submittals of upright sprinklers replacing.
(BMC 7-01-50-901.2, IFC 105.4.2)
Note: Incorporating the T.I. work with changing out of the entire floors fire sprinklers, may affect the Tenant and its occupancy since any related problem in the replacements, will affect the other.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/31/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/31/2005 | | 3/31/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/31/2005 | | DONE |
|
|
|
|
Application received | | | 3/22/2005 | | |
|
|
|
|