Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00160
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 100 E IDAHO ST
Project NameSPR MISTI UG & SUPPLY REROUTE
Customer Number 
ePlanReview 
Description
MISTI UNDERGOUND & SERVICE SUPPLY REROUTE FOR ST. LUKE'S MRI and BD SHELL & CORE ADDITION * To reroute the existing 6" underground into the MSTI/St. Lukes connecting tunnel corridor, running south and across the connecting tunnel corridor into the MISTI fire sprinkler control room, while abandoning the existing underground and overhead supply piping in the fire sprinkler room. This fire protection work shall comply with the IFC 2003 and the permit review comments and conditions list; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00094.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/16/20056/16/20056/16/2005PPASS
DetailsForrest France
Fire sprinkler finaled, Troy Cobbley has tested the flow switch during alarm testing under the associated fire alarm permit fir05-00232.
INSP-Sprinkler Rough-in/Hydro4/26/20054/27/20054/27/2005PPART
DetailsForrest France
Underground fire supply piping within building passed rough-in inspection. Need to verify flow switch operation prior to final.
INSP-Supply line flush4/26/20054/27/20054/27/2005APASS
DetailsForrest France
Fire supply line flush satisfactory.
INSP-Sprinkler Rough-in/Hydro4/27/20054/27/20054/27/2005PPASS
DetailsForrest France
Underground fire supply hydrostatic test passed.
Issue and Print Permit  4/20/2005 DONE
Plan assigned to (Bill)3/22/2005 4/19/2005 DONE
Sprinkler Plan Check4/8/2005 4/19/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/19/2005 DONE
Override - Parcel Holds  4/19/2005  
Permit Ready to Issue  4/19/2005 DONE
Telephone call  4/19/2005 DONE
spoke with jeff anderson told him permit is ready and fees 4/19/05 3:45 pm BAS
Override - Parcel Holds  4/19/2005  
Inspection Record Card- Fire4/19/2005 4/19/2005 DONE
Plan resubmittals received  4/8/2005 DONE
Sprinkler Plan Check3/22/2005 3/31/2005 FAIL
DetailsBill Alexander
1. Plans are incomplete. Provide detailed clarification of required thrust protection on the underground supply entering the tunnel corridor. (BMC 7-01-50-901.2, IFC 105.4.2)

2. Plans are incomplete. Provide location and type of required earthquake bracing for the 6" main piped in the tunnel and through the riser room to point of replacement connection (fire pump supply-bottom ell). (BMC 7-01-50-901.2, IFC 105.4.2)

3. Submittal is incomplete. Provide clarification and locations of required flexure joints (for verification of E.Q. bracing addressed in Item #2 above).

4. Plans are incomplete. Provide type and location of hangers and its components supporting the pipe installing. (BMC 7-01-50-901.2, IFC 105.4.2)

5. Plans are incomplete. Provide location and size of any drain valves incorporating for trapped main/supply. (NFPA 13:8.15.2.5, BMC 7-01-50-901.2, IFC 105.4.2)

6. Submittal is incomplete. Provide manufacturers data submittals of all pertinent devices installing. (BMC 7-01-50:901.2, IFC 105.4.2)

7. Provide detail/information of transition from Ductile Iron to Schedule 10 steel. (NFPA 13-6.3.6*, 6.4.1, 6.4.5*, BMC 7-01-50-901.2, IFC 105.4.2)

8. Tunnel/Corridor requires a minimum construction separation for a type 1-A building from all other rooms and building (separations). Provide clearance and clarification of meeting this requirement for all penetrations made through rated fire barriers/walls. (IFC, BMC 7-01-50-901.2, IFC 105.4.2, 703, NFPA 13:A.9.3.4, A.9.3.4)
Miscellaneous action  3/31/2005 DONE
DetailsBill Alexander
Returned documents to permit desk for returning.
Telephone call  3/31/2005 DONE
tlk to jeff anderson that permit failed and needs to be picked up
Telephone call  3/31/2005 DONE
gave failed plans to treasure valley fire/3/31/05/mls
Application received  3/22/2005