INSP-Final Inspection | 1/11/2006 | 1/11/2006 | 1/11/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/8/2005 | 12/9/2005 | 12/9/2005 | P | PART |
Forrest France
|
|
|
The two added heads in the bakery to meet correct spacing requirements are satisfactory.
|
INSP-Final Inspection | 12/6/2005 | 12/7/2005 | 12/7/2005 | P | FAIL |
Troy Cobbley
|
|
|
Heads are overspaced in the bakery. Provide two additional heads as discussed.
|
INSP-Final Inspection | 9/29/2005 | 9/30/2005 | 9/30/2005 | P | FAIL |
Troy Cobbley
|
|
|
Revised plans not on site. No inspection done
|
Inspection Record Card- Fire | 6/21/2005 | | 6/21/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/21/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/10/2005 | | 6/20/2005 | | PASS |
Bill Alexander
|
|
|
6/10/2005 - Don Weland submitted changed sprinkler heads installed which are recalled by the manufacturer. Emailed response indicating they are not accepted.
6/15/2005 - Don Weland submitted revised manufacturer data submittals only. Requested:
1. Submit with a permit application (resubmittal) with revised scope of work indicating what you are now doing,
2. Include which manufacturer sprinkler model identified you are, or did install, since more than one is listed in the data,
3. Include revised sprinkler schedule & legend/s with symbols, SIN, description, type K-factor, temp, escutcheon and quantities, etc.
4. Two plans were submitted and each plan had legends. If each plan incorporated changes, then provide those changes for each,
5. Fax it to: ###-####.
6/15/2005
Recieved revised drawings.
|
Plan assigned to (Bill) | 6/10/2005 | | 6/20/2005 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 6/15/2005 | | 6/20/2005 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/20/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/20/2005 | | DONE |
|
|
|
tlk to trent bice ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 6/15/2005 | | DONE |
|
|
|
|
Case Summary | | | 6/15/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/3/2005 | 6/6/2005 | 6/6/2005 | A | FAIL |
Troy Cobbley
|
|
|
See city approved plans for locations of defiencies which include overspaced heads in the pharmacy and customer service/video rental
|
Issue permit | | | 5/25/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 5/24/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 5/24/2005 | | 5/24/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/24/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 5/12/2005 | | 5/23/2005 | | PASS |
Bill Alexander
|
|
|
|
Telephone call | | | 5/23/2005 | | DONE |
|
|
|
8:55am. Talked to "Chip" (John Armstrong) and requested he submit firew sprinkler head legend (FP-1) that matches the sprinklers installing (no correlation) and fax to: ###-####.
|
Plan assigned to (Bill) | 5/12/2005 | | 5/23/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/23/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/12/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 5/9/2005 | 5/10/2005 | 5/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Inspection stopped. No approval notes for plans. Head not shown on plans that has been installed under the overhead door. Dry pendants in coolers are Viking, not Central as shown on the plans. Pendant heads in the meat dept. are SIN3231 which are not the
|
INSP-Sprinkler Rough-in | 5/10/2005 | 5/10/2005 | 5/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
This entry is a supplement to the earlier entry. Pendant heads in the meat department that have been changed out are not shown on the approved plans as part of the work.
|
INSP-Sprinkler Rough-in | 5/10/2005 | 5/10/2005 | 5/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
This entry is a supplement to the earlier entry. Pendant heads in the meat department that have been changed out are not shown on the approved plans as part of the work.
|
Sprinkler Plan Check | 4/26/2005 | | 5/3/2005 | | PASS |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 4/26/2005 | | 5/3/2005 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/3/2005 | | 5/3/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/3/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/3/2005 | | DONE |
|
|
|
called spoke with chip permit is ready and fees 5/3/05 3:11pm LEM
|
Issue and Print Permit | | | 5/3/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/26/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/24/2005 | | 3/24/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/24/2005 | | DONE |
|
|
|
|
Telephone call | | | 3/24/2005 | | DONE |
|
|
|
tlk to trent ###-#### that permit and fees are ready to be picked up
|
Case Summary | | | 3/24/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/24/2005 | | DONE |
|
|
|
|
Application received | | | 3/23/2005 | | |
|
|
|
|
Plan assigned to (Bill) | 3/23/2005 | | 3/23/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/23/2005 | | 3/23/2005 | | PASS |
Bill Alexander
|
|
|
Faxed permit application
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/23/2005 | | DONE |
|
|
|
|