INSP-Final Inspection | 12/16/2005 | 12/19/2005 | 12/19/2005 | P | PASS |
Forrest France
|
|
|
Items on correction notice have been completed, alarm tested satisfactory, permit finaled.
|
INSP-Final Inspection | 12/14/2005 | 12/15/2005 | 12/15/2005 | P | FAIL |
Forrest France
|
|
|
Vent tube at duct detector 1st floor is incorrect, smoke detector at the electrical room 2nd floor is too close to the wall, 2nd and 3rd floor strobe in the common corridor is too low, pull station at the north roof is not functional, horn in the mech. penthouse is not operational, need to update map reflecting actual location of the floor control valves for the sprinkler system, not a complete inspection at this time, need to repair defficiencies and call for reinspect.
|
Issue and Print Permit | | | 3/29/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 3/25/2005 | | 3/28/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/28/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|