Permit Information
Permit NumberFIR05-00185
StatusFinaled
Name PEAK ALARM
Site Address 5010 -5350 W OVERLAND RD
Project Namealm - HILLCREST SHOPPING CNTR
Customer Number 
ePlanReview 
Description
FIR05-00185 is to upgrade the existing fire alarm system (a single FACP) in the shopping center. (A copy of the upgrade agreement is on sheet F0.0.) A required manual fire alarm system is required in the northwest corner of the center (Mike's Restaurant, Primerica, Calvary Chapel, Stage Coach Theatre and Heart and Home) due to the A occupancy load. The remainder of the shopping center will consist of sprinkler monitoring, HVAC shutdown and cooking hood monitoring. Albertson's has its' own FACP and will be allowed to do so due to the fire barriers that separate fire areas.

The associated building permit (BLD 05-00660) is to extend existing 1-hr fire barrier walls through the canopy at the Hillcrest Shopping Center. The fire barriers will define separate fire areas for alarm systems. The new 1-hr fire barrier walls installed in the canopy shall be continuous through concealed spaces within the canopy and shall extend at least 18" below the canopy ceiling. Existing fire barrier walls shall be extended and upgraded, if necessary, to create a complete separation where it is deficient. Openings shall be protected and penetrations fire stopped. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (HILLCREST SHOPPING CENTER - CODE UPGRADE) This building is required to be fire sprinklered because it is an unlimited area building.

FIR05-00186 is to provide monitoring of a cooking hood and two duct smoke detectors for HVAC shutdown to the existing required sprinkler monitoring system.

The associated building permit (BLD 04-02195) is to convert an existing 4,450 square foot tenant space to a restaurant (4,085 square foot main floor and 365 square foot mezzanine). This space was formerly used for retail sales. Work is to include interior nonbearing walls, two restrooms accessible to the disabled, a grease hood and duct, a hood and duct over a dishwasher, a stairway to serve the existing mezzanine, upgraded and extended 1-hr fire barrier walls, and interior finishes all per the approved drawings and the plan review report on file. Within the remodel area, the fire sprinkler heads shall be located or relocated to comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (MONGOLIAN BISTRO - HILLCREST SHOPPING CENTER) This building is fire sprinklered for unlimited area of the building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  9/20/2005 DONE
Left a message for Mark Knowles (CSHQA out of the office until 9/26) that we have not received the Phase II submittal that was to be submitted by 9/1/2005. I asked that he return my call.
Agreement of Future work2/24/20051/1/20079/6/2005 DONE
Phase III of a III Phase Upgrade Agreement
Agreement of Future work2/24/20051/1/20079/6/2005 DONE
Phase I of a III Phase Upgrade Agreement.
Agreement of Future work2/24/20051/1/20069/6/2005 DONE
Phase II, of a III Phase Upgrade Agreement
INSP-Sprinkler Rough-in/Hydro9/2/20059/6/20059/6/2005 PASS
Fire alarm permit finaled.
DOC - Permit Finaled  9/6/2005 DONE
Permit finaled.
INSP-Final Inspection8/31/20059/2/20059/2/2005 CANC
No time today for this re-inspection, spoke with Ray to schedule for next week.
INSP-Final Inspection8/31/20059/1/20059/1/2005 PART
Completed testing of all devices and re-tested defficient items. All issues are satisfactory except the outside bell at Fred Meyers and Mongolian Bistro failed to function properly.
INSP-Final Inspection8/30/20058/31/20058/31/2005 PART
Inspected devices at the dollar store riser, dry cleaners, golf store, knox box, and all relocated pull stations in the west portion of shopping center.
INSP-Final Inspection8/29/20058/30/20058/30/2005 CANC
No time available for this inspection today, ray to schedule for tomorrow at 9:00am per our agreement.
INSP-Final Inspection8/25/20058/26/20058/26/2005 PART
Finished testing central riser stack, tested east riser, tested tamper in pit, need to install and test outside electric bell at riser next to mongolian bistro, testing complete through FP1.4.
INSP-Final Inspection8/24/20058/25/20058/25/2005 CANC
Spoke with the contractor to reschedule this inspection for friday the 26th due to time constraints today.
INSP-Final Inspection8/22/20058/24/20058/24/2005 FAIL
Antifreeze tamper at the golf store failed to operate correctly, two wet system inspectors test connections lack a proper test orfice, additional tamper at west riser is not shown on plan, the riser next to Mongolian Bistro lacks an outside bell, all items tested today through sheet FP1.3, the liquor store on sheet FP1.4 tested okay. Need to provide copy of signal verification as requested.
INSP-Final Inspection8/22/20058/23/20058/23/2005 FAIL
One horn strobe device in the Stage Coach theater seating area failed to operate, an additional horn strobe is required in the lounge area at Mikes Restaurant due to a mirrored soffit obstruction, one storage room adjacent to the lounge is missing notification, several pull stations are mounted 1/2" too high, todays inspection completes all areas up to the first west fire separation wall.
INSP-Final Inspection8/19/20058/22/20058/22/2005 PART
Testing today included Fred Meyer, Honks and Heart and Home stores. The outside bell at Fred Meyers failed to operate, a manual pull station at the main exit from the Heart and Home store is mounted too high, all other items in these areas tested today are acceptable.
INSP-Alarm Testing8/18/20058/19/20058/19/2005 PART
All that was tested today and passed was the phone lines, battery draw, the smoke detector above the main facp and the interconnection between the fire alarm panel and the NAC panels. What did not pass today was the loss of a/c power was not detected on the stagecoach NAC panel and the NAC panels are not labeled to match the map and the plans. They need to show up on the panel as #1, #2 and #3. Also loss of batteries comes in labeled as a gate valve. These points between the NAC's and the main facp need to be retested to verify that the description/device matches the action. Per the alarm contractor the tamper switch in the pit is off line due to construction of a water line that damaged that part of the circuit.
INSP-Final Inspection8/17/20058/18/20058/18/2005 CANC
DetailsTroy Cobbley
ray; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Inspection Record Card- Fire8/12/2005 8/12/2005 DONE
Permit Ready to Issue  8/12/2005 DONE
Telephone call  8/12/2005 DONE
lft vm with bill herbert 09-2900 that permit and fees are ready to be picked up
Issue and Print Permit  8/12/2005 DONE
Alarm Plan Check  8/12/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/12/2005 DONE
Plan resubmittals received  8/9/2005 DONE
INSP-Final Inspection7/7/20057/7/20057/7/2005PFAIL
DetailsTroy Cobbley
Did not start inspection. Contractor stated that the three NAC panels are not sync'd as required. Hood in Mike's Restraunt was not finished. Existing sprinkler devices had not been pre-tested.
CHANGE STATUS TO (ISS)  7/7/2005 DONE
Alarm Plan Check  6/28/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  6/28/2005 DONE
Permit Ready to Issue  6/28/2005 DONE
Telephone call  6/28/2005 DONE
lft vm ###-#### for bill herbert that permit and fees are ready to be picked up
Plan resubmittals received  6/23/2005  
Issue and Print Permit  4/4/2005  
Inspection Record Card- Fire4/1/2005 4/1/2005 DONE
Telephone call  4/1/2005 DONE
Spoke with Bill and told him that permits are ready & fees///4/1/05 4:05pm BAS
Plan assigned to (Mary)3/31/2005 4/1/2005 DONE
Telephone call  4/1/2005 DONE
I called Bob Brady to advise that notification appliances will be required within the "mall" area, because it is part of the building and fire area, and is part of the means of egress. He agrees and will revise plans adn bring them in this morning so we wil not need to issue a "failed" review. I also pointed out that the code does not require notification within "unoccupied" spaces within the buidling, e.g. the unleased tenant space. He prefers to put a/v devices within the unleased space anyway as that way it will be easier to modify the system for a new tenant.
Alarm Plan Check  4/1/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/1/2005 DONE
Permit Ready to Issue  4/1/2005 DONE
Application received  3/31/2005  
Inspection Record Card- Fire4/1/2005