Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR05-00187
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 915 W IDAHO ST
Project NameSPR HURTADO FURNITURE
Customer Number 
ePlanReview 
Description
(HURTADO FURNITURE STORE - PLAZA 121 - STE 101) To modify the existing fire sprinkler system for the tenant improvement work and creation of a 6,079-ft/2 retail sales furniture store (3,734-ft/2 1st story and 2,345-ft/2 basement). This space is located on the 1st story and basement (northwest corner) of an existing 6 story building. Fire sprinkler work is related to the removal of all CPVC in the affected area in the basement and installation of steel pipe with new sprinklers from wall furring, gypsum board soffits, suspended ceilings, a new floor opening between the basement and 1st story, a new non-egress stairway, interior nonbearing walls, the basement non-rated corridor extended to the existing enclosed stairway located at the alley. This building is fire sprinklered in lieu of opening protection at the alley, rated corridors, basement enclosure, elevator lobbies, etc. It is also fire sprinklered because it has occupied floors more than 55 feet above the sidewalk and to allow one stairway to egress through a nonrated lobby on the 1st floor. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00053.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20056/1/20056/1/2005APASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Final Inspection5/27/20055/27/20055/27/2005PPART
DetailsForrest France
Final pending water curtain at exit discharge basement level.
INSP-Sprinkler Rough-in/Hydro4/20/20054/20/20054/20/2005PFAIL
DetailsForrest France
Hangers on pipe supplying pendents exceeding 100 psi. static must be within 1' of the end. Some 1'' CPVC is not yet removed in basement area suite 3B furniture store. Head in basement storage room is too far below beam. Upright is blocked by copper pi
Plan assigned to (Bill)4/1/2005 4/13/2005 DONE
Sprinkler Plan Check4/4/2005 4/13/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/13/2005 DONE
Inspection Record Card- Fire4/13/2005 4/13/2005 DONE
Permit Ready to Issue  4/13/2005 DONE
Telephone call  4/13/2005 DONE
tlk to gerald ebeling ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  4/13/2005 DONE
Plan resubmittals received  4/4/2005  
Application received  4/1/2005