Permit Information
Permit NumberFIR05-00190
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR MEDICAL IMAGING SL & CENTR
Customer Number 
ePlanReview 
Description
ST LUKES & CENTRAL WING-GROUND FLOOR & SUB BASEMENT (MEDICAL IMAGING) To remodel 26,150-ft//2 of existing areas currently used as surgery support space for medical imaging per approved plans. Fire sprinkler work is related to new interior walls to create exam, treatment, recovery, medical imaging suite corridor walls. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02203.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20061/25/20061/25/2006APASS
DetailsForrest France
Fire sprinkler work completed satisfactory, permit finaled.
INSP-Sprinkler Rough-in/Hydro1/3/20061/3/20061/3/2006PPART
DetailsForrest France
Overhead rough-in at area as marked on approved plan is acceptable, escutcheons at hard lid ceilings are missing, a 2" threaded tee is leaking- location marked on plans.
INSP-Sprinkler Rough-in/Hydro12/19/200512/19/200512/19/2005PPART
DetailsForrest France
Overhead rough-in is good for cover at four hard lid areas as marked on approved plans.
INSP-Sprinkler Rough-in/Hydro12/9/200512/9/200512/9/2005PPART
DetailsForrest France
Overhead rough-in at the mens locker room and rooms adjacent to the elevator as marked on approved plans are acceptable to cover.
INSP-Sprinkler Rough-in12/1/200512/2/200512/2/2005APART
DetailsForrest France
Specials lab main and one head in hard lid area are good for cover.
Sprinkler Plan Check11/29/2005 11/29/2005 PASS
Plan modification approved.
PLANS/APPL TAKEN TO FRONT DESK  11/29/2005 DONE
Inspection Record Card- Fire11/29/2005 11/29/2005 DONE
Permit Ready to Issue  11/29/2005 DONE
Telephone call  11/29/2005 DONE
left mess that permit is ready
Issue and Print Permit  11/29/2005 DONE
INSP-Sprinkler Rough-in/Hydro11/15/200511/15/200511/15/2005PPART
DetailsForrest France
Overhead rough-in in two separate corridor locations as circled on approved plans are good for cover.
Plan resubmittals received  10/31/2005 DONE
INSP-Sprinkler Rough-in/Hydro10/20/200510/21/200510/21/2005AFAIL
DetailsTroy Cobbley
The sprinkler piping doesn't match installation for the Special Services area. Contractor needs to resubmit plans that match installation. A 1 1/2" loop has been installed and 1 1/4" branchline is being used to supply new pendants that is not shown on the plans.
INSP-Sprinkler Rough-in/Hydro10/6/200510/6/200510/6/2005PPART
DetailsForrest France
Overhead piping inspected for cover at soffits in the specials lab.
INSP-Sprinkler Rough-in9/15/20059/16/20059/16/2005APART
DetailsForrest France
Overhead rough-in for system 10 west side sheet FP1 is acceptable to cover.
INSP-Sprinkler Rough-in/Hydro9/15/20059/15/20059/15/2005PCANC
DetailsForrest France
No time for this inspection today, have rescheduled with contractor for friday am 9/16.
INSP-Sprinkler Rough-in/Hydro8/3/20058/3/20058/3/2005PFAIL
DetailsForrest France
One hanger is missing on an arm over for the pendent head in the H/K closet. Three other hard lid areas as marked on the approved plans are okay to cover.
INSP-Conference7/28/20057/28/20057/28/2005PCANC
DetailsForrest France
Inspection is re-scheduled for tomorrow a.m per Phil Doble.
INSP-Final Inspection6/28/20056/28/20056/28/2005APART
DetailsTroy Cobbley
Early Completion area "C" passed. Heads corrected in GS202 and GS203. Inspected two additional pendant heads which have been circled and dated on city approved plans.
INSP-Final Inspection6/27/20056/27/20056/27/2005PCANC
DetailsForrest France
Cancel inspection per Phil Doble, not ready for inspection today.
INSP-Sprinkler Rough-in/Hydro6/20/20056/20/20056/20/2005PFAIL
DetailsForrest France
Pendent heads are blocked by proximity to columns in womens lockers GS202, two heads are supplied by a 1" feed in womens GS203- see note #12 on plan review comments for requirements. Heads circled in red on approved plans are the only areas inspected at this time.
Override - Parcel Holds  4/14/2005  
Inspection Record Card- Fire4/14/2005 4/14/2005 DONE
Telephone call  4/14/2005 DONE
tlk to brodie ###-#### that permit and fees are ready to be picked up
Override - Parcel Holds  4/14/2005  
Permit Ready to Issue  4/14/2005  
Override - Parcel Holds  4/14/2005  
Issue and Print Permit  4/14/2005 DONE
Plan assigned to (Bill)4/1/2005 4/13/2005 DONE
Sprinkler Plan Check4/1/2005 4/13/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/13/2005 DONE
Case Summary  4/1/2005 DONE
Application received  4/1/2005  
Inspection Record Card- Fire11/29/2005