INSP-Final Inspection | 5/12/2005 | 5/12/2005 | 5/12/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler finaled.
|
Issue and Print Permit | | | 4/22/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 4/5/2005 | | 4/7/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/6/2005 | | 4/7/2005 | | PASS |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 4/7/2005 | | 4/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/5/2005 | | 4/6/2005 | | FAIL |
Bill Alexander
|
|
|
Basic plan requirements are needed to provide a clear and precise IFC code review in meeting Boise Municipal Code
7-01-50 ADDITION TO SECTION 901.2, CONSTRUCTION DOCUMENTS.
Please resubmit and include the following minimum information:
1. What floor in this facility is this work is being performed on?
2. What is the location/area on the floor this work is being performed at?
3. What kind of hanger attachments you intend to use?
4. Is the existing lines gridded or tree piping?
5. What is the size of the existing line kicked back on the existing 2" main?
6. What is the size of the new line being kicked back off the existing 2" main?
7. Out of 10 sprinklers available on the manufacturers data sheets, which pendant head you are incorporating?
8. Address the occupancy use (name) of the area the line is being added.
|
Miscellaneous action | | | 4/6/2005 | | DONE |
|
|
|
Emailed designer (Tom Easton) requesting more information.
|
Application received | | | 4/5/2005 | | |
|
|
|
|
INSP-Final Inspection | 5/4/2005 | 5/5/2005 | | A | |
|
|
|
vadell Note: add 3 sprinklers head ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|