Permit Information
Permit NumberFIR05-00205
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 600 N ROBBINS RD
Project NameIDAHO ELK'S REHAB
Customer Number 
ePlanReview 
Description
To provide required automatic detection and total notification in the remodeled space on the first floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, door release, elevator recall/shutdown, cooking hood monitoring and notification throughout.

The associated building permit (BLD 04-01705) is to remodel a 2,974 sq.ft. area in the north east portion of the 1st floor per approved plans. A "Letter of Compliance" is required. Work includes construction of a two (2) hour fire-barrier wall along the east side of the new hyperbaric chamber room area. This remodel will convert approximately 1,500 sq. ft. from "B" occupancy to become part of the existing 7,576 sq. ft. "I1.2" creating a 9,076 sq. ft., "I" occupancy suite. Construction of walls to be non-combustible framing with fire-rated sheetrock covering; interior finishes, cabinetry, electrical, mechanical, plumbing, sprinkler & alarm system upgrades to meet tenant needs and minimum codes. PC04-479/drs (HYPERBARIC FACILITY)(IDAHO ELK'S REHABILITATION HOSPITAL-1ST FLR) 3rd PLAN MODIFICATION 2/23/05 -
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/8/20056/9/20056/9/2005APASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection6/7/20056/8/20056/8/2005AFAIL
DetailsTroy Cobbley
Relocate and test the door holder, verify correct heights for all a/v's and repair/test fire dampers.
INSP-Final Inspection6/3/20056/6/20056/6/2005AFAIL
DetailsForrest France
Add smoke detection in room 118, add notification in office room 104 per note #7 on review comments, provide updated map at FACP, provide sign at room door containing FACP, adjust heights on AV's to meet reqirements of note #10.
Issue permit  4/27/2005 DONE
Plan assigned to (Mary)4/7/2005 4/26/2005 DONE
Alarm Plan Check  4/26/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/26/2005 DONE
Permit Ready to Issue  4/26/2005 DONE
Telephone call  4/26/2005 DONE
Spoke with Chris and told him that permit is ready & fees///4/26/05 2:50pm BAS
Inspection Record Card- Fire4/26/2005 4/26/2005 DONE
Telephone call  4/25/2005 DONE
Spoke with Greg Hayne at Elks Rehab, the cooking hoods are being monitored by the FA system as a supervisory. I explained the code requirement of the signal to be alarm. Greg stated that it would be no problem to have that reprogrammed. I told him that I would include it in the notes for this permit and the inspector will verify the three (3) hoods during the inspection for the first floor.
Telephone call  4/21/2005 DONE
Called Greg Hayne, Elks, to discuss the cooking hood monitoring as a supervisory input to the FA system. I left a message.
Application received  4/7/2005