Information based on query as of Thursday, September 24, 2026.
Permit Information
Permit NumberFIR05-00212
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON DOCK CANOPY
Customer Number7643
ePlanReview 
Description
MICRON BUILDING #15 - DOCK CANOPY COVER - To install an wet, antifreeze loop fire sprinkler system under a new 20'x40' (8000-ft/2) steel framed canopy with metal roof, constructed over an existing concrete dock and attached to the northeast corner of Building #15. The system will be connected to an existing wet system located in Building #15. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-0593.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/6/20056/6/20056/6/2005PPASS
DetailsTroy Cobbley
Fire sprinkler permit passed.
INSP-Final Inspection6/2/20056/2/20056/2/2005PFAIL
DetailsTroy Cobbley
Provide one piece fittings, need hydro test and anti-freeze signs and annual inspection tag. Need to review all review notes as this turned into just a preliminary inspection.
Case Summary  5/13/2005 DONE
INSP-Final Inspection5/12/20055/12/20055/12/2005PCANC
DetailsForrest France
Wrong permit number called in, not ready for this inspection. Actual inspection done was for cleanroom in fab (addition of 3 heads).
Issue and Print Permit  4/26/2005 DONE
Plan assigned to (Bill)4/11/2005 4/25/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  4/25/2005 DONE
Permit Ready to Issue  4/25/2005 DONE
Inspection Record Card- Fire4/25/2005 4/25/2005 DONE
Telephone call  4/25/2005 DONE
E-mailed Paul that permit is ready & fees///4/25/05 9:25am BAS
Plan resubmittals received  4/20/2005  
Sprinkler Plan Check4/25/2005 4/20/2005 PASS
DetailsBill Alexander
Per requirements of review comments attached.
Sprinkler Plan Check4/11/2005 4/14/2005 FAIL
DetailsBill Alexander
1. Plan submittals are incomplete. The use of antifreeze solutions shall be in conformity with state and local health regulations. Where sprinkler systems are supplied by potable water connections, the use of antifreeze solutions other than water solutions of pure glycerin (C.P. or U.S.P. 96.5 percent grade) or propylene glycol shall not be permitted.
a. Provide clarification on what kind of water supply system this system will be attached. Is it attached to a potable water supply source?
b. Provide the type of "antifreeze" installing.
c. Provide the capacity of system AND quantity antifreeze installing (in gpm) and freezing point (in ºF) proposed.
(BMC 7-01-50-901.2, IFC 105.4.2, NFPA 13-7.5.1.1, 7.5.2.1, 7.5.2.4*, 14.1.3[42])

2. Plan submittals are incomplete. The designer does not clarify the required system antifreeze loop arrangement design and components installing.
a. Provide correct arrangement detail/s of the antifreeze loop installing, which includes, dimensioning, elevations, control valves, checks (backflow), expansion chambers, required fittings, signage, tamper supervision and any other relevant and required components relating to the type of antifreeze loop installing. If connected to a public water drinking systems then "Idaho Rules For Public Drinking Water - 58.01.08" and Department of Labor and Industrial Services installation requirements must apply and be addressed (shown) on the plans. (NFPA 13-7.5.1.1, 7.5.3, BMC 7-01-50-901.2, IFC 105.4.2, 106, 107.2.2, 901.6, 903.3.3)

3. Include data submittals of any relevant and required pertinent antifreeze system components and the listing of each. (NFPA 13-14.1.3[23, 41])

4. Plan submittals are incomplete. Provide system piping hanger locations. (NFPA 13-14.1.3[22])

5. Plan submittals are incomplete. It appears the canopy slopes down from the building out, approximately 9". Include a section detail through the canopy that provides clarification of slope, structural beam locations and beam depths of which affect fire sprinkler location placements, coverage and etc. Include any light fixtures or other relevant building components that affect fire sprinkler spray characteristics. (NFPA 13-14.1.3[37], BMC 7-01-50-901.2, IFC 105.4.2)

6. Plan submittals are incomplete. This is an addition to an existing system.
a. Provide the system identification (other than it is wet).
b. Provide the maximum floor area this one sprinkler system riser or combined system riser is protecting. Maximum allowed is per NFPA 13-8.2.1.

7. Plan submittals are incomplete. Design would appear to meet minimum densities for the hazard class protecting but assumptions is not verification of meeting minimum code or acceptance of the responsibility for the same. Provide system hydraulic calculations meeting NFPA 14.4. (BMC 7-01-50-901.2, IFC 105.4.2)
Miscellaneous action  4/14/2005 DONE
Returned (faxed) submittal to permit desk for calling and returning.
Telephone call  4/14/2005 DONE
EMAIL PAUL AND MAX THAT SUBMITTAL FAILED TO BE PICKED UP
Application received  4/11/2005