Permit Information
Permit NumberFIR05-00217
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4840 N CLOVERDALE RD
Project NameSPR SLRMC INTERNAL MEDICINE
Customer Number 
ePlanReview 
Description
(SAINT LUKES INTERNAL MEDICINE BUILDING) To install a complete light hazard, wet and dry pipe overhead fire sprinkler systems within a new 11,274-ft/2, single story, wood framed, medical office building, with a 600-ft/2 covered driveway entry canopy and a 459-ft/2 covered patio area. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-00217.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/23/20058/23/20058/23/2005PPASS
DetailsForrest France
Calculations for spacing have been verified. Fire sprinkler permit finaled.
Plan assigned to (Bill)8/19/2005 8/23/2005 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/23/2005 DONE
Inspection Record Card- Fire8/23/2005 8/23/2005 DONE
Permit Ready to Issue  8/23/2005 DONE
Issue and Print Permit  8/23/2005 DONE
Sprinkler Plan Check8/19/2005 8/23/2005 PASS
DetailsBill Alexander
Major pipe modification and revised head spacing calculation verifications.
INSP-Final Inspection8/19/20058/19/20058/19/2005PFAIL
DetailsTroy Cobbley
Still need to verify that the sprinkler spacing in the conference room and the additional dry pendants are approved with resubmittals.
Plan resubmittals received  8/19/2005 DONE
INSP-Final Inspection8/17/20058/17/20058/17/2005PFAIL
DetailsTroy Cobbley
Forward flush passed but need to certify the backflow preventor, provide verification of the spacing in the conference room and the additional dry pendants with bill as previously requested. Verify that the valve for the ball drip in the pit is open
INSP-Sprinkler Rough-in/Hydro7/7/20057/7/20057/7/2005PPASS
DetailsTroy Cobbley
Wet system hydro test passed. Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro6/29/20056/30/20056/30/2005PPASS
DetailsTroy Cobbley
24 hour air test passed on dry system
INSP-Sprinkler Rough-in/Hydro6/29/20056/29/20056/29/2005PPART
DetailsTroy Cobbley
Started 24 hour air test with 50psi on guage.
INSP-Sprinkler Rough-in/Hydro6/16/20056/16/20056/16/2005PPASS
DetailsTroy Cobbley
200 lb hydro test on the dry pipe system passed.
INSP-Sprinkler Rough-in/Hydro6/7/20056/7/20056/7/2005PPART
DetailsTroy Cobbley
The remaining part of the dry system passed. Not all arm overs have been installed and will need inspected. Final head spacing to be checked when t-bar is installed.
INSP-Sprinkler Rough-in/Hydro6/3/20056/3/20056/3/2005PPART
DetailsTroy Cobbley
See city approved plans for location where wet system can be covered as of 6/3/05.
INSP-Sprinkler Rough-in/Hydro6/1/20056/1/20056/1/2005PPART
DetailsTroy Cobbley
The dry system rough-in is ok except for one head needs to be added in the south east room. Contractor needs to get with Bill Alexander to see if a resubmittal will be required for this head and the three other dry uprights added at each of the entrances.
Sprinkler Plan Check5/20/2005 5/31/2005 PASS
DetailsBill Alexander
05/27/2005 8:00am-Email to Jeff Anderson:
Requested completed calc cover sheets.
Requested information on where plan changes were made in this project.
05/31/2005 11:15am-Converstation with John Graves.
Plan assigned to (Bill)5/20/2005 5/31/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/31/2005 DONE
Permit Ready to Issue  5/31/2005 DONE
Inspection Record Card- Fire5/31/2005 5/31/2005 DONE
Telephone call  5/31/2005 DONE
Spoke with Jeff Anderson and told him that permit is ready & fees///5/31/05 1:10pm BAS
Issue and Print Permit  5/31/2005 DONE
Plan resubmittals received  5/20/2005  
INSP-Sprinkler Rough-in/Hydro5/19/20055/19/20055/19/2005PPART
DetailsTroy Cobbley
Sprinkler piping in the west drive thru canopy can be covered. As stated in the previous inspection entry, plans need to be resubmitted due to changes.
INSP-Supply line flush5/17/20055/17/20055/17/2005PPASS
DetailsTroy Cobbley
Underground supply line flush and underground hydro test passed. I had contractor measure leakage. 5 1/2 quarts was allowed and it lost approx. 2 1/2 to 3 quarts
INSP-Sprinkler Rough-in5/17/20055/17/20055/17/2005PFAIL
DetailsTroy Cobbley
I started rough-in inspection on the dry system at the request of the onsite sprinkler fitter but could not do the inspection due to pipe routing and sizing not matching approved plans. Upright heads are not spaced in accordance with NFPA 13 for obstruct
Issue and Print Permit  4/25/2005 DONE
Plan assigned to (Bill)4/13/2005 4/22/2005 DONE
Sprinkler Plan Check4/21/2005 4/22/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/22/2005 DONE
DetailsBill Alexander
Inspection Record Card- Fire4/22/2005 4/22/2005 DONE
Permit Ready to Issue  4/22/2005 DONE
Telephone call  4/22/2005 DONE
lft ms with secretary for jeff anderson ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check4/13/2005 4/21/2005 FAIL
DetailsBill Alexander
1. Provide 3 copies of the manufacturer's data submittals, 4" backflow.

2. Provide 3 copies of the manufacturers data submittals the Dry Pipe Valve (if more than one available on the sheet/s-identify)

3. Provide 3 copies of the manufacturer's data submittals of the "air maintenance device".

4. Provide 3 copies of the manufacturer's data submittals of the "compressor".

5. Attic is identified as "obstructed" with the definition "Wood Joist Construction." This definition is different than "Wood Truss." Relating to you section view on FP3, I do not see wood joists, but I do see wood trusses. Your hanger detail (same sheet) addresses Wood Trusses also? If obstructed, clarify and indicate the affected areas on a plan (minimum 3 - 8½" X 11's), with details where the deflector will be places from the roof. If your have made a mistake, and the wood truss 2" X 4" or 6"s, etc., are the impairment suggesting, then the "3 times rule" will apply.

6. Calc Area #1 is using 11.2.3.2.3 (reduced area of operation), which will require sprinkler protection in all unprotected sprinkler pocket/s. Otherwise revise your calculations with a minimum 1500-ft/2 area of operation and leave the pocket/s unprotected. Correct and resubmit a minimum of 3 (your choice).
Plan resubmittals received  4/21/2005  
DetailsBill Alexander
Application received  4/13/2005