Permit Information
Permit NumberFIR05-00222
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 11580 W FAIRVIEW AVE
Project NameSPR UG COLTRIN BUILDING
Customer Number 
ePlanReview 
Description
COLTRIN BUILDING (SHELL) -To install 227'-0" +- of 6" C-900 PVC underground fire service supply. The connection is in Fairview Ave running north to the property line (by others) and continues under this permit to a riser room identified as #103, then west approximately 5'-0" from the building. The piping changes to Ductile Iron Class 50 (min), under the footing and up through the floor, near the outside of the building, to approximately 6" above the finished floor with a "Uniflange" transition fitting. This work is for the fire protection of an 18,490-ft/2, two story, type V-B, fully fire sprinklered office/retail shell building. The fire sprinklers will be used for area and story increase. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-02020.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/15/20062/15/20062/15/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro11/21/200511/22/200511/22/2005ACANC
DetailsTroy Cobbley
No time for inspection
INSP-Sprinkler Rough-in5/17/20055/17/20055/17/2005PPASS
DetailsTroy Cobbley
Underground supply piping is ok to cover
INSP-Sprinkler Rough-in5/13/20055/16/20055/16/2005PPASS
DetailsTroy Cobbley
Underground supply line is ok to cover with bedding. Needs inspection before final cover.
Issue and Print Permit  4/27/2005 DONE
Inspection Record Card- Fire4/26/2005 4/26/2005 DONE
Inspection Record Card- Fire4/26/2005 4/26/2005 DONE
Permit Ready to Issue  4/26/2005  
Telephone call  4/26/2005 DONE
lft ms with receptionist for tom ###-#### that permit and fees are ready to be picked up
Plan assigned to (Bill)4/15/2005 4/25/2005 DONE
Sprinkler Plan Check4/15/2005 4/25/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/25/2005 DONE
Application received  4/15/2005