INSP-Final Inspection | 1/4/2006 | 1/5/2006 | 1/5/2006 | A | PASS |
Forrest France
|
|
|
The remaining portions of the alarm permitted work passed final inspection.
|
CHANGE STATUS TO (ISS) | | | 1/4/2006 | | DONE |
|
|
|
was finaled on 12/22/05 but not a complete inspection per Jim
|
INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 | A | PASS |
Forrest France
|
|
|
Defficient issues have been corrected, inspection passed.
|
INSP-Final Inspection | 12/20/2005 | 12/21/2005 | 12/21/2005 | A | FAIL |
Forrest France
|
|
|
Strobe in the staff break room is blocked by a wall not shown on plans, coverage in this area is incomplete, relocate or add an additional device, all other items tested okay.
|
Issue and Print Permit | | | 10/21/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/20/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/20/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/20/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/20/2005 | | 10/20/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/20/2005 | | DONE |
|
|
|
Left voice message for James that permit is ready & fees///10/20/05 3:45pm BAS
|
Plan resubmittals received | | | 10/12/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/12/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2005 | 9/27/2005 | 9/27/2005 | P | PASS |
Forrest France
|
|
|
Items on correction notice have been completed, fire alarm passed inspection.
|
INSP-Final Inspection | 9/23/2005 | 9/26/2005 | 9/26/2005 | A | FAIL |
Forrest France
|
|
|
SD is overspaced in file room, SD in two adjacent rooms as marked on plans are too close to HVAC diffusers, one strobe in restroom with drop ceiling is mounted too high, all other items tested okay, provide latest resubmittals at next inspection.
|
Permit Ready to Issue | | | 9/16/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/16/2005 | | 9/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/16/2005 | | DONE |
|
|
|
Spoke with Jim and told him that permit is ready & fees///9/16/05 9:25am BAS
|
CHANGE STATUS TO (ISS) | | | 9/16/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/16/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/15/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/15/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/7/2005 | | DONE |
|
|
|
|
INSP-Alarm Testing | 6/22/2005 | 6/23/2005 | 6/23/2005 | A | PART |
Forrest France
|
|
|
Fire alarm inspection satisfactory for exit corridor, women's lockers and restrooms, and southeast portion of area C.
|
(F) Reprint permit | | | 6/22/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/22/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/21/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/21/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/21/2005 | | |
|
|
|
|
Telephone call | | | 6/21/2005 | | DONE |
|
|
|
tlk to jim shilton ###-#### that permit is ready to be picked up
|
Plan resubmittals received | | | 6/16/2005 | | DONE |
|
|
|
|
Case Summary | | | 6/16/2005 | | DONE |
|
|
|
|
INSP-Conference | 5/31/2005 | 6/1/2005 | 6/1/2005 | A | DONE |
Forrest France
|
|
|
Done. Walk through with Phil Doble and Dave Hannah area C. Discussed project phasing and inspection schedule.
|
Plan assigned to (Mary) | 4/21/2005 | | 5/12/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/12/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/12/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/12/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/12/2005 | | 5/12/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/12/2005 | | DONE |
|
|
|
Spoke with Jim and told him that permit is ready & fees///5/12/05 10:11am BAS
|
Issue and Print Permit | | | 5/12/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/5/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/2/2005 | | FAIL |
|
|
|
Resubmittal required. No comments written, Jim Shilton copied my notes and comments from the city copy.
|
Application received | | | 4/21/2005 | | |
|
|
|
|
Case Summary | | | 4/21/2005 | | DONE |
|
|
|
|