Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR05-00255
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1211 S COLE RD
Project Namealm - LDS Temple FA upgrade
Customer Number 
ePlanReview 
Description
To upgrade an existing fire alarm system. The required manual fire alarm system includes sprinkler monitoring, automatic detection (heat detectors will be installed in the attic spaces, a high sensitivity smoke detector (air sampling) will be implemented in the "domed" areas of the building, this is considered primary detection and the design information is included in the package) and smoke detectors will be installed in all corridors, elevator recall/shutdown (elevator controllers will be upgraded next year, the new modules will be installed at this time, a FA permit will be required to connect, test and inspect) and notification throughout.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20059/19/20059/19/2005 PASS
DetailsSam Rogers
Building map has been provided. NFPA 72 certificate has been signed. Permit is complete and finaled.
DOC - Permit Finaled  9/19/2005 PASS
Permit finaled 9/19/2005
CHANGE STATUS TO (ISS)  8/26/2005 DONE
Corrected improper final action.
INSP-Final Inspection8/22/20058/22/20058/22/2005 PART
DetailsSam Rogers
Duct smoke detectors installation approved. Now all complete except still need to provide a building map(s) at FACP of all FA initiating points; to be verified 8/26 or 8/29 as notified by Fire Sentry when completed.
INSP-Final Inspection8/1/20058/8/20058/8/2005PFAIL
DetailsTroy Cobbley
As per sam rogers, two additional duct smoke detectors are required
INSP-Alarm Testing7/22/20057/25/20057/25/2005APART
DetailsTroy Cobbley
earl; Phone #: ###-#### Final inspection by SLR; left correction notice of 10 items, none of serious nature which would prevent occupancy(SLR). A temporary occupancy was given with Sam Rogers permission until items that he has noted have been corrected.
Alarm Plan Check  5/27/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/27/2005 DONE
Plan resubmittals received  5/27/2005 DONE
Received the requested information faxed from Randy Drake.
Inspection Record Card- Fire5/27/2005 5/27/2005 DONE
Permit Ready to Issue  5/27/2005 DONE
Telephone call  5/27/2005 DONE
lft ms with kevin ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  5/27/2005 DONE
Telephone call  5/26/2005 DONE
I requested battery, power supply and revised calculations from Randy Drake for the HSSD.
Alarm Plan Check  5/26/2005 FAIL
Resubmittal required. No written comments on this rejection. Many items from the first request had not been processed. I agreed to accept new plans, riser and calcs for the resubmittal.
Plan resubmittals received  5/26/2005 DONE
Plan resubmittals received  5/20/2005  
Case Summary  5/20/2005  
Alarm Plan Check  5/9/2005 FAIL
Resubmittal required. Faxed comments to John Lopez (FSS) and Mint Peterson (ECI).
Case Summary  4/28/2005  
Application received  4/28/2005  
Plan assigned to (Mary)4/28/2005