INSP-Final Inspection | 9/19/2005 | 9/19/2005 | 9/19/2005 | | PASS |
Sam Rogers
|
|
|
Building map has been provided. NFPA 72 certificate has been signed. Permit is complete and finaled.
|
DOC - Permit Finaled | | | 9/19/2005 | | PASS |
|
|
|
Permit finaled 9/19/2005
|
CHANGE STATUS TO (ISS) | | | 8/26/2005 | | DONE |
|
|
|
Corrected improper final action.
|
INSP-Final Inspection | 8/22/2005 | 8/22/2005 | 8/22/2005 | | PART |
Sam Rogers
|
|
|
Duct smoke detectors installation approved. Now all complete except still need to provide a building map(s) at FACP of all FA initiating points; to be verified 8/26 or 8/29 as notified by Fire Sentry when completed.
|
INSP-Final Inspection | 8/1/2005 | 8/8/2005 | 8/8/2005 | P | FAIL |
Troy Cobbley
|
|
|
As per sam rogers, two additional duct smoke detectors are required
|
INSP-Alarm Testing | 7/22/2005 | 7/25/2005 | 7/25/2005 | A | PART |
Troy Cobbley
|
|
|
earl; Phone #: ###-#### Final inspection by SLR; left correction notice of 10 items, none of serious nature which would prevent occupancy(SLR). A temporary occupancy was given with Sam Rogers permission until items that he has noted have been corrected.
|
Alarm Plan Check | | | 5/27/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/27/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/27/2005 | | DONE |
|
|
|
Received the requested information faxed from Randy Drake.
|
Inspection Record Card- Fire | 5/27/2005 | | 5/27/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/27/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/27/2005 | | DONE |
|
|
|
lft ms with kevin ###-#### that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 5/27/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/26/2005 | | DONE |
|
|
|
I requested battery, power supply and revised calculations from Randy Drake for the HSSD.
|
Alarm Plan Check | | | 5/26/2005 | | FAIL |
|
|
|
Resubmittal required. No written comments on this rejection. Many items from the first request had not been processed. I agreed to accept new plans, riser and calcs for the resubmittal.
|
Plan resubmittals received | | | 5/26/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/20/2005 | | |
|
|
|
|
Case Summary | | | 5/20/2005 | | |
|
|
|
|
Alarm Plan Check | | | 5/9/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to John Lopez (FSS) and Mint Peterson (ECI).
|
Case Summary | | | 4/28/2005 | | |
|
|
|
|
Application received | | | 4/28/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 4/28/2005 | | | | |
|
|
|
|