Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00259
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4709 W STATE ST
Project NameSPR OH COLLISTER COMMUNITY CH
Customer Number 
ePlanReview 
Description
COLLISTER COMMUNITY CHURCH ADDITION * To install a complete automatic, single, 364 gallon, dry pipe system throughout a 5,640-ft/2, one story, type V-B new addition and a 2,828-ft/2, two story (small 280-ft/2 2nd story classroom), type V-B existing Sanctuary. The fire sprinklers are used for area and additional story in the existing building. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR05-00113. This permit is attached to building permit: BLD04-02139.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20059/23/20059/23/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled. Insulation has been installed in the existing dormers and the standard heads re-installed.
INSP-Final Inspection9/19/20059/20/20059/21/2005AFAIL
DetailsTroy Cobbley
Need hydraulic calcs for the dormer areas
INSP-Final Inspection9/16/20059/16/20059/16/2005PFAIL
DetailsTroy Cobbley
There are still obstructions to the upright sprinkler heads above the ceiling in the existing chapel and I need calculations for the attic heads in the existing dormers.
INSP-Final Inspection9/14/20059/15/20059/15/2005PCANC
DetailsTroy Cobbley
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
INSP-Sprinkler Rough-in/Hydro9/12/20059/12/20059/12/2005PPART
DetailsTroy Cobbley
See approved plans for locations of remaining deficiencies. Also still need head wrench, sign on control valve and forward flush
INSP-Sprinkler Rough-in9/7/20059/9/20059/9/2005ACANC
DetailsForrest France
No time for this inspection today, spoke with Mike from TV to schedule for monday 9/12 per our agreement.
INSP-Sprinkler Rough-in/Hydro8/24/20058/24/20058/24/2005PPART
DetailsForrest France
Dry system 24 hour air test passed with the maximum allowable loss of 1.5 psi, air pressure at 2:00 p.m 8/24/05 was 40.5 psi.
INSP-Sprinkler Rough-in/Hydro8/23/20058/23/20058/23/2005PPART
DetailsForrest France
Begin 24 hour air test of the dry system at 1:55 p.m 8/23/05 at 42psi.
INSP-Sprinkler Rough-in/Hydro8/18/20058/19/20058/19/2005PPASS
DetailsTroy Cobbley
hydro test for overhead passed
INSP-Sprinkler Rough-in/Hydro6/9/20056/10/20056/10/2005APASS
DetailsTroy Cobbley
Sprinkler piping in new addition is ok to cover.
INSP-Sprinkler Rough-in6/7/20056/7/20056/7/2005PPASS
DetailsTroy Cobbley
Tenting in new addition is passed. Storage areas and concealed combustible areas still need addressed
INSP-Sprinkler Rough-in/Hydro6/6/20056/7/20056/7/2005APART
DetailsTroy Cobbley
See city approved plans for locations of deficiencies. Lower system south end not installed yet. Hydro test passed but was only partial test.
INSP-Sprinkler Rough-in/Hydro6/2/20056/3/20056/3/2005AFAIL
DetailsTroy Cobbley
Plans on job site are only have partial approvals. Updated plans are not on site. Could not do hydro because guage only showed 180lbs of pressure. No inspection done.
Issue and Print Permit  5/31/2005 DONE
Sprinkler Plan Check5/18/2005 5/26/2005 PASS
DetailsBill Alexander
Plan assigned to (Bill)5/26/2005 5/26/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/26/2005 DONE
Permit Ready to Issue  5/26/2005 DONE
Telephone call  5/26/2005 DONE
lft message with message company ###-#### that permit and fees are ready to be picked up
Plan resubmittals received  5/18/2005 DONE
Issue permit  5/16/2005 DONE
Permit Ready to Issue  5/13/2005 DONE
Inspection Record Card- Fire5/13/2005 5/13/2005 DONE
Telephone call  5/13/2005 DONE
called left message for gerald permit is ready and fees
Plan assigned to (Bill)4/29/2005 5/12/2005 DONE
Sprinkler Plan Check4/29/2005 5/12/2005 PART
DetailsBill Alexander
1. Manufacturer data submittals are missing. No data submittals provided on the Reliable Model "F3QR", Q.R., SSP, D.P., 5.6 K-factor, R5714 sprinklers, of which 13 are addressed as being installed in this facility.
2. Manufacturer data submittals are missing. No data submittals provided on an air compressor/supply and regulating appurtenance. Where a dry pipe system is supplied by an automatic air compressor system and any device or apparatus used for automatic maintenance of air pressure shall be of a type specifically listed for such service. If more than one is listed in the documents, identify the exact related one incorporating. (BMC 7-01-50-901.2, NFPA 13-7.2.6.6.1)
3. It was found that a dry pendent (possibly more which were addressed) is installed on a drop nipple (see following reference location). Limitations are included in product installation instructions for potential accumulation of scale and sediment building up at the sprinkler when installed on a drop nipple. This installation practice is not accepted since corrosion/sediment would fall into the drop nipple piping and affect the required flow/pressure of the dry pendant sprinkler operation.
4. The designer incorporating the wrong purpose, usage and installation design of a "Return Bend". The purpose of return bends, (covered under 8.14.18.1 through 8.14.18.4) is to prevent collection of scale and sediment from normal scale and sediment from corrosion in being pushed into the drop nipples, which developed from normal environmental moisture trapped in dry piping that, can plug or affect normal sprinkler operation flows/pressures. Return bends shall not be taken off the bottom of branch lines or mains. Also "Armovers" on any kind of riser nipple is not a "Return Bend", but would be considered a "Swing Joint", if exceeding some degree of pipe length, (the higher possibility of accumulated scale/sediment build up). This AHJ will allow the use of return bends to be within the limit of 2'-0" length (the standard requirement for a hanger). Any length of piping exceeding that length (measured center to center) will require a return bend on the down elbow to the pendent head! Remember, pendent sprinklers installed on return bends only permitted where both the sprinklers and the return bends are located in a heated area. (Reference NFPA 13- 8.14.18)
5. Foyer A101 (plan FP-2, Lower Reflected Ceiling detail) will require head adjustment to allow for fire sprinkler coverage of all walls. Red-lined on plan.
6. The Existing Sanctuary Lower Level piping designed are proving a density of .10 over 225 ft/2 per head, yet the actual PIPE spacing input in the calculations is averaging 140 ft/2? The conflicting input procedure does not provide accurate friction loss (C-factor and velocities) data in the calculation analysis report and is unacceptable form of calculating for an area/density maximum spacing! This area shall be installed exactly as shown and no spacing allowed exceeding 140-ft/2 allowed for these pendant heads or reverification shall be provided. (NFPA 13-8.5.2.1, 14.4.4.3.3, 14.4.4.5, and 14.1.3 [34]).
7. In this review, construction information is lacking relating to the uprights in this Lower Piping Existing Sanctuary cavity. With lack of construction information, the upright cavity sprinkler coverage will be limited to 130-ft/2 maximum spacing per NFPA 13-8.6.2.2.1(a) or corrected and detailed information shall be provided.
8. Outside control shown on FP-2, but no outside control is shown or provided on the on the riser? Provide corrected plans addressing this BMC 7-01-53, 903.1.3 requirements.
PLANS/APPL TAKEN TO FRONT DESK  5/12/2005 DONE
Case Summary  4/29/2005 DONE
Application received  4/29/2005